Normally Closed Input
A normally closed fire alarm input from an
FACP should be wired across FAI- and FAI_P.
A jumper wire must be connected across
FAI- and FAI P.
When the contact is open, this activates the
FAI in the AC42 which disables 12V/24V
power to all 4 relay outputs. In other words
all wet locks will be effectively dry while the
FAI is triggered.
Normally Open Input
A normally open fire alarm input from an
FACP should be wired across FAI+ and FAI-.
When the contact is closed, this activates
the FAI in the AC42 which disables 12V/24V
power to all 4 relay outputs. In other words
all wet locks will be effectively dry while the
FAI is triggered.
Installation
FAI set up 1/2
FAI+ and FAI_P must be locally jumpered
in this configuration.
Important
AC42
AC42