8
Introduction
AC42 Technical Specifications
Power
Consumption
60W maximum
AC Power Input
100-240VAC
50/60Hz
1.5A maximum
Inputs
2x REX dry inputs per door
1x DPI dry input per door
2x auxiliary dry inputs
Readers
1x reader port (Verkada/RS-485 or Wiegand) per door
Reader current consumption must be < 250mA per reader
Note: max of 4 readers can be powered simultaneously
Relay Outputs
1x wet or dry relay per door
Wet relay switch-selectable power:
12V operation 700mA max
24V operation 350mA max
Dry relay max pass-through power:
24VDC @ 2A (resistive load)
2x auxiliary dry relays
AUX Power 1x 12V @ 250mA
Dimensions 417 x 321 x 116.25mm
Weight 6.35kg
Operating
Temperature
0°C - 50°C
5 - 90%
Humidity
Compliance
FCC Part 15 Class A, ICES-3 Class A, CE, UKCA, RCM, VCCI, UL
294, CAN/ULC 60839-11-1, UL 62368-1, CSA C22.2 No. 62368-1,
IEC 62368-1, NDAA
Connectivity
Ethernet: 10/100Mbps RJ-45 for network connection
USB 2.0
Included
Accessories
Lock key and flat head screwdriver
Mounting Options Mounting plate and 4 wood screws