4.3.1 Paralleling Cable Kit
Module-to-module communication cables are required for 1+N parallel systems. A kit with RJ-45
connectors ships with each multi-module EXL S1 UPS. At least one kit is required for each added UPS
module; the number of kits required is one fewer than the number of UPS modules in the 1+N system (for
example, six UPS modules would require five kits).
NOTE: Verify appropriate strain relief for all parallel communication cables to ensure no tension or
pressure on the RJ-45 to AP30-XP71 and AP30-XP72 connections.
Parallel communication cables must be selected from one of the suppliers to be compatible with the RJ-45
connector on the EXL S1. Vertiv Part # 564556P1 supplied or ordered with multi-module systems. Contact
factory for details. Approved CAT6 cable suppliers:
ABA, Part #TSR2404N70GY
Belden, Part #7953A
Comtron Cable LLC, Part #CAT 6 Plenum F/UTP
Primus, Part #CAT 6 FTP
4.3.2 Multi-Bus Synch Module (MBSM)
This module is available to support six or up to 11 UPS modules, and is generally configured to synchronize
all modules to a reference bus (e.g., bypass line). See the manual for this module for more details.
Vertiv | EXL S1 Installer Guide
38

Table of Contents

Other manuals for Vertiv Liebert EXL S1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert EXL S1 and is the answer not in the manual?

Vertiv Liebert EXL S1 Specifications

General IconGeneral
BrandVertiv
ModelLiebert EXL S1
CategoryUPS
LanguageEnglish

Related product manuals