EasyManua.ls Logo

Vertiv Liebert RX - Configuration 4-Three Units; Configuration 5-Four Units; Figure 2 Configuration 2 and Configuration 3-Two Liebert RX Units

Vertiv Liebert RX
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert
®
RX
Remote Distribution Cabinet User Manual | 7
Figure 2 Configuration 2 and Configuration 3—Two Liebert RX units
1.5.4 Configuration 4—Three Units
This three-unit configuration has two units attached back-to-back with a third unit attached to
the side. It is 36" wide and 24" (610mm) deep. These units are free-standing and can be set on a
raised floor. Refer to Figure 3.
1.5.5 Configuration 5—Four Units
This four-unit configuration has two units attached back-to-back with one unit attached to each
side. It is 48" wide and 24" (610mm) deep. These units are free-standing and can be set on a raised
floor. Refer to Figure 3.
RX17000
Rev. 1
CONFIGURATION 3
Side-by-Side
CONFIGURATION 2
Back-to-Back
NOTES:
1. Units are ordered and shipped separately.
Units can be attached in the field as shown.
2. Side-by-side units are not free-standing. They
must be attached to a wall or other support.
Mounting hardware supplied by others.
3. Hardware to attach units to each
other is factory-supplied.
4. Shown with optional monitoring display.
5. Configuration 2 requires front and rear
service access.
12.93"
(328mm)
25.86"
(657mm)
23.75"
(603mm)
23.75"
(603mm)
47.5"
(1207mm)
78.74"
(2000mm)
78.74"
(2000mm)
6. Configuration 3 requires front service access.
7. Service access clearance dimensions:
36" (914mm) for units up to 150V to ground
42" (1067mm) for units over 150V to ground
8. Clearance above the unit for cooling air flow: 18"
(460 mm) minimum
9. Clearance below for cables:12" (305mm)
minimum.

Table of Contents

Related product manuals