12 Chapter 2 Installation Instruction
NetSure 531 A41, NetSure 531 A91 Subrack Power system User Manual
See Table 2-6 for the dry contact terminal definition.
Table 2-6 Dry contact terminal definition
Name of double-layer port
Common contact of relay 1
Common contact of relay 2
Common contact of relay 3
Common contact of relay 4
Common contact of relay 5
Common contact of relay 6
Common contact of relay 7
Common contact of relay 8
The definition of dry contact function can be set through controller.
The specifications of the dry contact ports are as follows:
Digital inputs: 8-route, opto-isolation, the alarm and high/low level are definable (high level: 20V ~ 60V, low level: less
than 1V).
Digital output: 8-route, relay isolation, maximum: 30Vdc 1A, 125Vac 0.5A; 60W; minimum: 10uA @ 10Vdc, alarm is
definable.