Chapter 1 Introduction 5
NetSure 801 AG1 Power Supply System User Manual
Negative terminal
Positive terminal
Front
(b) Top view
Figure 1-7 HOD
2. Low ohmic distribution unit (LOD)
Dimensions (unit: mm): 132.5 (H) × 584 (W) × 250 (D)
Weight: 9.3kg
Rated current: 360A
In a standard LOD, the rated current of one MCB can be 6A ~ 40A (breaking capacity 6kA), or 50A ~ 63A (breaking
capacity 4.5kA), or 80A ~ 125A (breaking capacity 10kA).
Each LOD can be equipped with at most twenty-eight 18mm MCBs or eighteen 27mm MCBs, as shown in Figure 1-8.
DC positive terminal
Load MCB
Figure 1-8 LOD
3. Fuse unit
Rated current: 1600A
The breaking capacity of NT00, NT2 and NT3 fuses is 100kA. Four types of fuse units are described below:
1) Type 1
Dimensions (unit: mm): 427 (H) × 584 (W) × 353.5 (D)
Fuse unit type 1 is suitable for NT2 and NT3 fuses. It can accommodate at most six NT2 or NT3 fuses, or six fuses
combined of NT2 and NT3 fuses, as shown in Figure 1-9.
Figure 1-9 Fuse unit type 1
2) Type 2
Dimensions (unit: mm): 325 (H) × 584 (W) × 353.5 (D)
Fuse unit type 2 is suitable for NT00 fuses. It can accommodate at most 11 NT00 fuses, as shown in Figure 1-10.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv NetSure 801 AG1 and is the answer not in the manual?

Vertiv NetSure 801 AG1 Specifications

General IconGeneral
BrandVertiv
ModelNetSure 801 AG1
CategoryPower Supply
LanguageEnglish

Related product manuals