BACNET NETWORK SETTINGS
BACnet network screen shows when BACnet MS/TP is selected in wired protocol parameter.
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
COM address
Default value: 254
Communication Address
Room Controller networking address.
Default value of 254 disables BACnet communication for the Room Controller.
Range: 0 to 254
Network units
Default value: SI
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally
on the Room Controller.
Imperial: Network units shown as Imperial units.
SI: Network units shown as International Metric units.
Choices: Imperial or SI
Network lang.
Default value: English
Network Language
Network language/object names transmitted over network.
Choices: English, French or Spanish
Baud rate
Default value: Auto
BACnet Baud Rate
Leave the value at Auto unless instructed otherwise as this automatically detects
BACnet baud rate.
Choices: Auto, 115200, 76800, 57600, 38400, 19200 and 9600
BACnet status
Read Only
BACnet Status
Read Only value shows if a BACnet Network is detected or not.
Display Readings: Online or Ofine
BACnet PRate
Default value: 4
BACnet Poll Rate
Rate at which a BACnet stack is processed, in milliseconds.
Range: 1 to 5.