SETPOINTS 2/2
PARAMETER DETAILS
Conguration Parameters Default Value Signicance and Adjustments
Default heat
Default value: 72°F (22°C)
Default Heating Setpoint
Used for hospitality applications in stand-alone mode only to reset the occupied
setpoints when a new guest enters the room.
When the Room Controller is in unoccupied mode, any movement detected by
a wired, wireless or local PIR sensor changes the occupancy mode to occupied
modes and uses the “Default Heating Setpoint” as the new occupied setpoints.
NOTE: This functionality is only valid when Stand-by mode = Offset and
“Setpoint Func” is set to “Attached”.
Range: 65 to 80°F (18.5 to 26.5°C)
Min. deadband
Default value: 3°F (1.5°C)
Minimum Deadband
Temperature offset between the Cooling and Heating setpoints to ensure that
Cooling setpoint is always warmer than the Heating setpoint.
Cooling setpoint ≥ (Heating setpoint + Deadband)
Range: 2 to 5°F (1.0 to 2.5°C)
Max heating
Default value: 90°F (32°C)
Heating Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Heating setpoints limit.
Range: 40 to 90°F (4.5 to 32.0°C)
Min. cooling
Default value: 54°F (12°C)
Cooling Setpoint Limit
Minimum Occupied, Unoccupied, Standby and Override Cooling setpoint limit.
Range: 54 to 100°F (12.0 to 37.5°C)
Dehum. SP
Default value: 50%RH
Dehumidification Setpoint
Used only if dehumidication sequence is enabled.
Range: 30 to 95% RH