IMPORTANT INFORMATION
WARNING WARNING
Read and understand all instructions •
before attempting to perform maintenance
on any Victaulic piping products.
Wear safety glasses, hardhat, and foot •
protection.
Failure to follow these instructions could
result in serious personal injury, property
damage, and/or product failure.
Depressurize and drain the piping •
system before attempting to remove,
adjust, or perform maintenance on any
Victaulic piping products.
Failure to follow this instruction could
result in serious personal injury and/or
property damage.
REMOVING THE SYSTEM FROM SERVICE
CAUTION
Any activities that require taking the •
valve out of service may eliminate the fire
protection provided.
Before servicing or testing the system, •
notify the authority having jurisdiction.
Consideration of a fire patrol should be •
given in the affected areas.
Failure to follow these instructions could
result in serious personal injury and/or
property damage.
1. Notify the authority having jurisdiction, remote station alarm moni-
tors, and those in the affected area that the system is being taken
out of service.
2. Open the water supply main drain valve fully to flush the water
supply of any contaminants.
3. Close the water supply main drain valve.
Water Supply Main
Control Valve
4. Close the water supply main control valve to take the system out of
service.
The following instructions are a guide for removing and replacing the diaphragm in Series 764, 768,
and 769 FireLock NXT
Fire Protection Valves. It is important to replace the diaphragm with a new,
Victaulic-supplied diaphragm of the correct diameter to ensure proper valve operation.
I-NXT.DIA_1
Series 764, 768 and 769
REPLACING THE DIAPHRAGM IN SERIES 764, 768, AND 769 FIRELOCK
NXTFIRE PROTECTION VALVES
I-NXT.DIAREPLACEMENT KIT INSTRUCTIONS
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_A

Questions and Answers

  • J
    Jennifer SmithAug 12, 2025
    Why does the Victaulic FireLock NXT 764 Control Unit valve operate without sprinkler activation?
    • W
      William McintoshAug 12, 2025
      If the Victaulic Control Unit valve operates without sprinkler activation, it could be due to a loss of air pressure in the system or trim. Check for leaks and ensure the AMTA is operating correctly. Installing a low-air supervisory switch might also help. Alternatively, the air compressor's pressure switch might be set too low, or the compressor isn't working right. Try increasing the “ON” setting of the air compressor’s pressure switch and inspect the air compressor.
  • A
    Andrea RoseAug 19, 2025
    What to do if water is leaking from the drip check in the Victaulic FireLock NXT 764 alarm line?
    • W
      Warren RussellSep 12, 2025
      If water is leaking from the drip check in the alarm line of your Victaulic Control Unit, this could be because water is getting past the clapper seal and into the intermediate chamber of the valve. Inspect the clapper seal and valve body seat ring for any physical damage or foreign material. Another possible reason is water is under the clapper seal. Inspect the clapper seal to ensure no water is underneath it. If water is present, remove and replace the seal.
  • T
    Thomas FarleyAug 27, 2025
    Why is air leaking from the drip check in the Victaulic FireLock NXT 764 Control Unit alarm line?
    • K
      Karen SmithAug 27, 2025
      If air is leaking from the drip check in the alarm line of your Victaulic Control Unit, it may be because air is getting past the clapper seal and into the intermediate chamber of the valve. Check the clapper seal and valve body seat ring for physical damage and foreign material. Another cause could be water under the clapper seal. Inspect the clapper seal, and if water is present, remove and replace the seal.
  • S
    schultzalexSep 4, 2025
    How to fix a Victaulic FireLock NXT 764 Control Unit clapper that won't latch closed?
    • K
      krausejasonSep 4, 2025
      If the clapper of your Victaulic Control Unit won't latch closed, it could be because there is no water pressure on the diaphragm. Check the water pressure in the diaphragm charge line and ensure the restrictor is clean. Another potential cause is that the Auto Drain is not set. Set the Auto Drain by pulling up on the Auto Drain Sleeve.

Victaulic FireLock NXT 764 Series Specifications

General IconGeneral
CategoryControl Unit
Maximum Working Pressure300 psi (20.7 bar)
MaterialDuctile Iron
CoatingOrange Enamel
Connection TypeGrooved
UL ListedYes
FM ApprovedYes
ModelFireLock NXT 764 Series
StandardsUL, FM
Sizes2" to 8"