What to do if the Victaulic Control Unit water motor alarm is not ringing?
- EElizabeth BarnettAug 4, 2025
If the Victaulic Control Unit's water motor alarm isn't ringing or is weak, first ensure that the holes in the seat ring aren't plugged to allow water into the intermediate chamber. Also, check that check valves isolate each valve's alarm line in the system, preventing leaks from another valve's alarm line drain. Finally, confirm the correct restrictor size is installed in the alarm line drain; if incorrect, replace it according to the trim drawing.