KEEP THESE INSTRUCTIONS WITH THE
INSTALLED VALVE FOR FUTURE REFERENCE
WARNING
Read and understand all instructions before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping products.
Depressurize and drain piping systems before attempting to install, remove, adjust, or perform maintenance on any Victaulic piping
products.
Wear safety glasses, hardhat, and foot protection.
Save this installation, maintenance, and testing manual for future reference.
Failure to follow instructions and warnings could cause system failure, resulting in death or serious personal injury and property damage.
INSTALLATION, MAINTENANCE, AND TESTING MANUAL I-768N
Series 768N FireLock NXT
Dry Valve
I-768N
REV_C

Questions and Answers

  • C
    Christine MorrisAug 17, 2025
    How to troubleshoot Victaulic 768N FireLock NXT valve operating without sprinkler activation?
    • A
      Amanda DavidsonAug 17, 2025
      If the valve of your Victaulic Control Unit operates without sprinkler activation, it might be due to a loss of air pressure in the system or trim, or the pressure switch on the air compressor might be set too low, or the compressor isn't working right. Check for leaks in the system and trim. Make sure the AMTA is working properly. Think about adding a low-air supervisory switch. Increase the “ON” setting of the air compressor’s pressure switch, and check the air compressor to ensure it's working as it should.
  • M
    meredithramirezAug 20, 2025
    What to do if water is leaking from the ball drip on the alarm manifold assembly of Victaulic 768N FireLock NXT?
    • P
      pwilliamsAug 20, 2025
      If water leaks from the ball drip on the alarm manifold assembly of your Victaulic Control Unit, it's likely because water is getting past the clapper seal and into the intermediate chamber of the valve. This means water is under the clapper seal. Check the clapper seal and valve body seat ring for any physical damage or foreign material. Inspect the clapper seal to ensure that no water is under it. If water is present, remove and replace the seal.
  • S
    Shawn HunterAug 23, 2025
    Why is air leaking from the ball drip on the alarm manifold assembly of Victaulic 768N FireLock NXT Control Unit?
    • K
      kim59Aug 23, 2025
      If air is leaking from the ball drip on the alarm manifold assembly of your Victaulic Control Unit, it indicates that air is passing the clapper seal and entering the valve's intermediate chamber, with water beneath the clapper seal. Inspect the clapper seal and valve body seat ring for physical damage or obstructions. Ensure no water is under the clapper seal; if present, remove and replace the seal.
  • B
    Brandon HayesAug 26, 2025
    What to do if Victaulic 768N FireLock NXT Control Unit Series 746-LPA Dry Accelerator does not set up properly?
    • M
      michael50Aug 26, 2025
      If the Series 746-LPA Dry Accelerator of your Victaulic Control Unit does not set up properly (you cannot get pressure on the upper gauge, and the button pops up immediately when pressure is introduced), it means the Series 746-LPA Dry Accelerator is installed upside-down. Remove it from the trim and turn it around, ensuring the vent seal “button” faces down (toward the actuator).
  • A
    Alexis McintyreAug 28, 2025
    Why the clapper of Victaulic 768N FireLock NXT Control Unit will not latch closed?
    • F
      frank40Aug 28, 2025
      If the valve clapper of your Victaulic Control Unit won't latch closed, it's likely due to no water pressure on the diaphragm or the auto drain not being set. Check the water pressure in the charge line and ensure the restrictor is clean. Set the auto drain by pulling up on the auto drain sleeve.
  • E
    Elizabeth WillisAug 31, 2025
    What to do if Victaulic Control Unit Series 746-LPA Dry Accelerator does not operate within a 0.3-Bar/5-psi pressure drop?
    • D
      Derrick RogersAug 31, 2025
      If the Series 746-LPA Dry Accelerator of your Victaulic Control Unit doesn't operate within a 0.3-Bar/5-psi pressure drop in system air pressure, it could be due to air pressure loss in the upper air chamber or a slow air decay rate in the system. Use soapy water on all joints around the Series 746-LPA Dry Accelerator to check for leaks and repair them. Also, ensure there are no restrictions in the remote system test valve (inspector’s test connection).
  • R
    rickey86Sep 2, 2025
    What to do if Victaulic 768N FireLock NXT Control Unit Series 776 Low-Pressure Actuator does not trip when air is released?
    • K
      Kelly HernandezSep 3, 2025
      If the Series 776 Low-Pressure Actuator of your Victaulic Control Unit does not trip when air in the system is released, there may be a restriction in the piping between the air manifold and the auto vent. Remove the air feed nipple and clear any debris. Clean the restrictor and strainer in the air manifold. Make sure no debris has accumulated in the air manifold ports, which could be restricting airflow.
  • L
    Lisa OwensSep 5, 2025
    Why is water leaking through the Series 776 Low-Pressure Actuator of Victaulic 768N FireLock NXT?
    • T
      Timothy WoodsSep 5, 2025
      If water is leaking through the Series 776 Low-Pressure Actuator of your Victaulic Control Unit, it may be because the air chamber isn't set, the strainer is clogged, or the diaphragm is ripped. Make sure the vent seal is set and the air chamber is pressurized. Replace the strainer screen.
  • B
    Brittany BarnesSep 8, 2025
    What to do if Victaulic 768N FireLock NXT Control Unit Series 776 Low-Pressure Actuator screw does not stay set?
    • T
      Taylor CunninghamSep 8, 2025
      If the Auto Vent Sleeve of the Series 776 Low-Pressure Actuator on your Victaulic Control Unit doesn't stay set in the “UP” position when pulled up, it could be due to insufficient air reaching the actuator or a broken seal. Try increasing the air pressure to the Series 776 Low-Pressure Actuator.
  • C
    camposjonathanSep 12, 2025
    Why Victaulic 768N FireLock NXT Control Unit valve operates without sprinkler activation?
    • C
      Crystal WardSep 12, 2025
      If the valve of your Victaulic Control Unit operates without sprinkler activation, it could be due to a loss of air pressure in the lower inlet chamber of the Series 746-LPA Dry Accelerator. Check for air loss at the lower chamber seal and turn the adjustment nut counterclockwise to seal any leaks. Also, check for leaks in the system and trim, and confirm that the AMTA is operating correctly.

Summary

Series 768 N FireLock NXT Dry Valve Installation Manual

Initial System Setup

Water Flow Alarm Test

Installer Safety Information

Hydrostatic Testing

Receiving the Shipment

Trim Dimensions

Trim Components - Exploded View Drawing

Internal Valve Components - Section View and Exploded View Drawings

Air Supply Requirements

Base- or Riser-Mounted Air Compressors

Recommendations for air supply from base or riser-mounted compressors.

Shop Air or Tank-Mounted Air Compressors

Guidance on using shop air or tank-mounted compressors for air supply.

Settings for Air Supervisory Pressure Switches and Alarm Pressure Switches

Specifications for setting pressure switches for system monitoring.

Resetting the System

Weekly External Inspection

Monthly External Inspection

Required Main Drain Test

Required Water Flow Alarm Test

Required Water Level and Low-Air Alarm Tests

Required Partial Operational Trip Test

Required Full Operational Trip Test

Required Internal Inspection

Section VI Maintenance Procedures

Removing and Replacing the Clapper Seal

Detailed guide for removing and installing the clapper seal.

Removing and Replacing the Clapper Assembly

Steps for disassembling and reassembling the clapper assembly.

Installing the Cover Plate Gasket and Cover Plate

Instructions for fitting the cover plate gasket and cover plate.

Removing and Replacing the Diaphragm

Guide on how to remove and install the valve diaphragm.

Cleaning the Cartridge in the Air and Priming Manifold Assemblies

Procedure for cleaning internal cartridges in manifold assemblies.

Replacing the Filter in Series 776 Low-Pressure Actuators

Steps for replacing the filter element in the low-pressure actuator.

Troubleshooting

Troubleshooting - System

Common problems and solutions related to the overall dry valve system.

Troubleshooting - Series 776 Low-Pressure Actuator

Specific issues and fixes for the Series 776 low-pressure actuator.

Troubleshooting - Series 746-LPA Dry Accelerator

Problems and solutions related to the Series 746-LPA dry accelerator.

Victaulic 768N FireLock NXT Series Specifications