Why does the Victaulic FireLock NXT 768 Control Unit valve operate without sprinkler activation?
- BBryan BrooksAug 5, 2025
If the Victaulic Control Unit valve operates without sprinkler activation, it could be due to a loss of air pressure in the system or trim. Check for leaks and ensure the AMTA is operating correctly. Installing a low-air supervisory switch might also help. Alternatively, the air compressor's pressure switch might be set too low, or the compressor isn't working right. Try increasing the “ON” setting of the air compressor’s pressure switch and inspect the air compressor.