HANG THESE INSTRUCTIONS ON THE
INSTALLED VALVE FOR EASY FUTURE REFERENCE
WARNING
• Failuretofollowinstructionsandwarningscancauseproduct
failure,resultinginseriouspersonalinjuryandpropertydamage.
• Readandunderstandallinstructionsbeforeattemptingto
installanyVictaulicpipingproducts.
• Wearsafetyglasses,hardhat,andfootprotection.
• Savethisinstallation,maintenance,andtestingmanualfor
futurereference.
Ifyouneedadditionalcopiesofanyliterature,orifyouhaveany
questionsconcerningthesafeinstallationandoperationofthis
product,contactVictaulic,P.O.Box31,Easton,PA18044-0031,
USA,Telephone:1-800PICKVIC,e-mail:pickvic@victaulic.com.
WARNING
INSTALLATION,MAINTENANCE,ANDTESTINGMANUAL
I-768
FireLockNXT™DryValve
SERIES768
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REV_D

Table of Contents

Other manuals for Victaulic FireLock NXT 768 Series

Questions and Answers

  • M
    Manuel NortonAug 4, 2025
    Why does the Victaulic FireLock NXT 768 Control Unit valve operate without sprinkler activation?
    • B
      Bryan BrooksAug 5, 2025
      If the Victaulic Control Unit valve operates without sprinkler activation, it could be due to a loss of air pressure in the system or trim. Check for leaks and ensure the AMTA is operating correctly. Installing a low-air supervisory switch might also help. Alternatively, the air compressor's pressure switch might be set too low, or the compressor isn't working right. Try increasing the “ON” setting of the air compressor’s pressure switch and inspect the air compressor.
  • A
    andersonkevinAug 11, 2025
    What to do if water is leaking from the drip check in the Victaulic FireLock NXT 768 alarm line?
    • A
      Amanda Flores MDAug 11, 2025
      If water is leaking from the drip check in the alarm line of your Victaulic Control Unit, this could be because water is getting past the clapper seal and into the intermediate chamber of the valve. Inspect the clapper seal and valve body seat ring for any physical damage or foreign material. Another possible reason is water is under the clapper seal. Inspect the clapper seal to ensure no water is underneath it. If water is present, remove and replace the seal.
  • M
    Matthew GrayAug 19, 2025
    Why is air leaking from the drip check in the Victaulic Control Unit alarm line?
    • D
      Danielle TaylorAug 19, 2025
      If air is leaking from the drip check in the alarm line of your Victaulic Control Unit, it may be because air is getting past the clapper seal and into the intermediate chamber of the valve. Check the clapper seal and valve body seat ring for physical damage and foreign material. Another cause could be water under the clapper seal. Inspect the clapper seal, and if water is present, remove and replace the seal.
  • B
    bturnerAug 27, 2025
    How to fix a Victaulic Control Unit clapper that won't latch closed?
    • A
      Amanda AllenAug 27, 2025
      If the clapper of your Victaulic Control Unit won't latch closed, it could be because there is no water pressure on the diaphragm. Check the water pressure in the diaphragm charge line and ensure the restrictor is clean. Another potential cause is that the Auto Drain is not set. Set the Auto Drain by pulling up on the Auto Drain Sleeve.

Summary

Hazard Identification

Installer Safety Instructions

Air Supply Requirements

Installation Procedures

System Operations and Tests

Placing the System in Service

Procedures for safely bringing the dry valve system into operational status.

Required Tests

Procedures for essential tests like main drain, water flow, and operational tests.

Required Operational (Trip) Tests

Detailed steps for performing partial and full operational (trip) tests on the dry valve.

Required Internal Inspection

Maintenance Procedures

Removing and Replacing the Clapper Seal

Detailed instructions for replacing the clapper seal and related parts.

Troubleshooting

Troubleshooting - Series 776 Low-Pressure Actuator

Diagnosing and resolving issues specific to the Series 776 Low-Pressure Actuator.

Troubleshooting - Series 746-LPA Dry Accelerator

Diagnosing and resolving issues specific to the Series 746-LPA Dry Accelerator.

Troubleshooting - System

Identifying and resolving general system-wide operational problems.