INSTALLER SAFETY INSTRUCTIONS
WARNING
Anexperienced,trainedinstallermustinstallthisproductinaccordancewithallinstructions.These•
instructionscontainimportantinformation.
Depressurizeanddrainthepipingsystembeforeattemptingtoinstall,remove,adjust,ormaintainany•
Victaulicpipingproducts.
Failuretofollowtheseinstructionscancauseproductfailure,resultinginseriouspersonalinjuryand/or
propertydamage.
GENERAL
1. Readandunderstandallinstructionsandrefertothetrim
diagramsbeforeproceedingwiththeinstallation,maintenance,
andtestingofthisVictaulicSeries768FireLockNXTDryValve.
2. Inspecttheshipment. Make sure all components are included
in the shipment and that all necessary tools are available for
installation.
3. Useonlyrecommendedaccessories. Accessories and equipment
that are not approved for use with this dry valve may cause
improper system operation.
4. Wearsafetyglasses,hardhat,footprotection,andhearing
protection. Wear hearing protection if you are exposed to long
periods of noisy job-site operations.
5. Preventbackinjury. Larger and pre-trimmed valves are heavy and
require more than one person or mechanical lifting equipment to
position and install the assembly. Always practice proper lifting
techniques.
6. Avoidusingelectricallypoweredtoolsindangerous
environments. When using electrically powered tools for
installation, make sure the area is moisture-free. Keep the work
area well lit, and allow enough space to accommodate proper
installation of the valve, trim, and accessories.
7. Watchforpinchpoints. Do not place fingers under the valve
body where they could be pinched by the weight of the valve. Use
caution around spring-loaded components (i.e. clapper assembly).
8. Keepworkareasclean. Cluttered areas, benches, and slippery
floors can create hazardous working conditions.
9. PROTECTTHESYSTEMFROMFREEZINGCONDITIONS.THE
VALVEANDSUPPLYPIPINGMUSTBEPROTECTEDFROM
FREEZINGTEMPERATURESANDMECHANICALDAMAGE.
10. IFTHEINLETWATERSUPPLYISINTERRUPTEDFORANY
REASON,ANDSYSTEMSUPPLYPRESSURETOTHEVALVE
DECREASES,MAKESURETHEDIAPHRAGMCHARGELINEIS
FULLYPRESSURIZEDBEFOREPLACINGTHESYSTEMBACK
INSERVICE.
MAINTENANCEANDTESTING
1. Notifytheauthorityhavingjurisdiction. Always notify the
authority having jurisdiction before performing any maintenance
that eliminates the fire protection provided by the system.
2. FollowNFPArequirementsforsystemtestingandinspection
schedules. The building owner or their representative is
responsible for inspecting the system in accordance with current
NFPA-25 requirements or in accordance with the requirements of
the local authority having jurisdiction (whichever is more stringent).
3. Depressurizeanddrainthesystemcompletelybeforeperforming
anymaintenance. Water under pressure can cause the cover plate
to blow off during removal if the system is not depressurized and
drained completely.
4. Protectthevalvefromfreezingtemperatures,foreignmatter,
andcorrosiveatmospheres. Any condition that might degrade the
system or affect system performance must be avoided.
I-768_2