159
5793 309 - 05
Vitotronic 100, GC1B / Vitotronic 300-K, MW1B Installation and Service
Components
Mixing Valve Motor Kit
Components:
H Mixing valve motor (not for flanged mixing valve)
H Connecting plug for the heating circuit pump
H Supply temperature sensor as contact temperature
sensor for measuring the supply temperature, with
connecting cable 19 ft. (5.8 m) long.
Changing the rotational direction (if required)
1. Insert 3-pin plug A in the mixing valve motor rotated
through 180°.
2. Check the rotational direction.
Manual mixing valve adjustment
Lift the motor lever, unhook the mixing valve handle
and pull plug A.

Mixing valve “Open”
Mixing valve “Closed”
Specification mixing valve motor
Rated voltage 120V~
Rated frequency 60 Hz
Power consumption 4 W
Permissible ambient temperature
H during operation 32 to 104°F (0 to +40°C)
H during storage and
transport -4 to +149°F (–20 to +65°C)
Legend
A Mixing valve plug
B Field wiring
C Connection to mixing valve adaptor