9
SYMPTOM POSSIBLE CAUSE
A
CTION
Cabinet has no power
Cabinet is not connected to mains
or main power switch is off
Check connection to mains,
connect power cable if necessary.
Check main power switch, turn on
if necessar
y
.
Fuse is blown Replace blown fuse.
Cabinet does not maintain set
temperature
Air curtain is blocked, resulting
from obstruction on suction grid
Load cabinets correctly. Do not
place products or price tags in
front of airflow.
Refer to section Loading cabinets
for cabinet loadin
g
instructions.
Air curtain is blocked, resulting
from blockage in honeycomb
Remove honeycomb and vacuum
the honeycomb.
Refer to section Cleaning
cabinets for cabinet cleaning
instructions.
Glass doors are not properly
closed
Make sure doors close properly.
If necessary, adjust glass doors
so there is a tight seal between
doors and cabinet chassis.
Refer to section Adjusting doors
on how to ad
j
ust doors.
Evaporator fans are not operating Make sure all evaporator fans are
operating. The evaporator fans
are located underneath the
bottom plates.
If the evaporator fans are not
operating, contact your nearest
service or
g
anisation.
Operating thermostat or limiter
thermostat is malfunctionin
g
Contact your nearest service
or
g
anisation.
6. Troubleshooting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Viessmann Tecto MD5 and is the answer not in the manual?

Viessmann Tecto MD5 Specifications

General IconGeneral
BrandViessmann
ModelTecto MD5
CategoryRefrigerator
LanguageEnglish

Related product manuals