15
Minimum clearances for 1 outdoor unit
Outdoor unit with 1 fan
A
B
A
B
a
b
c
d
d
b
200
Fig. 5
A
Air discharge
B
Air intake
d Minimum clearance for service and maintenance
Cable entry Dimensions in mm
a b c d
Above ground level ≥ 100 ≥ 100 ≥ 300 ≥ 1000
Below ground level ≥ 100 ≥ 400 ≥ 300 ≥ 1000
Outdoor unit with 2 fans
A
B
A B
a
b
c
d
d
b
200
Fig. 6
A
Air discharge
B
Air intake
d Minimum clearance for service and maintenance
Installation sequence
Installing the outdoor unit (cont.)
6199585
Installation