Operating and service instructions
for contractors
Viesmann
Vitomax HS
Type M73
Type M75
Type M93
Type M95
High pressure steam boiler
VITOMAX HS
5837984 GB 1/2019
Please keep safe.

Other manuals for Viessmann Vitomax HS M95

Questions and Answers

  • L
    Lisa WalshAug 15, 2025
    What to do if the burner does not start in my Viessmann Boiler?
    • E
      Eileen OrozcoAug 15, 2025
      If the Viessmann Boiler's burner doesn't start, first check if the mains isolator is switched ON to ensure voltage is present. If the burner fault indicator is illuminated, press the reset button on the burner control unit. Also, verify the fuel supply line for any obstructions and check the shut-off valves. Finally, examine the safety equipment, in case the safety chain has been activated.
  • J
    Jose AtkinsAug 18, 2025
    Why is my Viessmann Vitomax HS M95 discharging from the safety valve?
    • B
      Brandi LevyAug 18, 2025
      If the Viessmann Boiler's safety valve is discharging, verify that the discharge pressure matches the maximum permissible operating pressure; replace the safety valve if required. Inspect the pressure regulator and pressure limiter adjustments, correcting them if the operating pressure is too high. Clean the valve seat if it's contaminated, and clear any blockages in the water trap pipe.
  • A
    Ashley LewisAug 21, 2025
    What to do if the water level limiter switches off in my Viessmann Vitomax HS M95?
    • M
      Michael ThomasAug 21, 2025
      If the water level limiter switches off on your Viessmann Boiler, open the shut-off valve in the feedwater line. Also, check the mains water connection to ensure there is feedwater in the feedwater tank. You should also determine the cause of the damage to the water pump and water level controller in accordance with the installation instructions.
  • A
    amber45Aug 25, 2025
    How to lower the flue gas temperature in my Viessmann Vitomax HS M95?
    • J
      Jenna KellerAug 25, 2025
      If the flue gas temperature is too high in your Viessmann Boiler, clean the boiler to address any contamination on the flue gas and water sides that may be reducing heat transfer. Also, check the burner heating output to ensure that the rated boiler heating output is not exceeded.
  • H
    hmorrisonAug 28, 2025
    Why does the water level limiter keep switching off on my Viessmann Vitomax HS M95?
    • M
      Mia VaughnAug 28, 2025
      If the water level limiter switches off and you notice severe water level fluctuations in your Viessmann Boiler, drain water from the boiler and feedwater tank, then refill with treated water. Blow down more frequently, and check the water treatment system. Also, check and adapt the electrode length.
  • M
    Maxwell GonzalezAug 31, 2025
    How to fix high water level in my Viessmann Boiler?
    • M
      Mckenzie SosaAug 31, 2025
      If the water level is too high in your Viessmann Boiler, install a steam trap to ensure the steam distributor above the boiler is adequately drained. Additionally, check the electrode length, in case the water level is set too high.
  • J
    Jacob GarciaSep 3, 2025
    How to prevent oxygen corrosion in my Viessmann Vitomax HS M95?
    • L
      Lisa SmithSep 3, 2025
      To prevent oxygen corrosion on the water side of your Viessmann Boiler, check the water treatment system and injection system in accordance with VdTÜV guideline if you are topping up with unsuitable water. If the boiler is often taken out of service without being preserved, switch to standby (95 °C) instead of a complete shut down.
  • D
    dwilsonSep 7, 2025
    Why is there steam knocking in my Viessmann Vitomax HS M95's condensate container?
    • K
      Kevin MurphySep 7, 2025
      If you hear steam knocking inside the condensate container or feedwater tank of your Viessmann Boiler, install or clean the check valve (observe the flow direction) because the check valve in the feedwater line might be missing or faulty. Identify and repair any faulty steam trap in the system. Reduce steam pressure, as U-bends might buckle.
  • B
    Bryan FowlerSep 12, 2025
    What causes steam hammer inside a Viessmann Boiler?
    • K
      kwashingtonSep 12, 2025
      If there's steam hammer inside your Viessmann Boiler, connect the feedwater line to the correct connector, ensuring that feedwater is fed in at the feedwater connector.

Summary

Safety Instructions

Safety Instructions for Working on the System

Provides essential safety guidelines for performing tasks on the boiler system.

Information

Functions

Shutdown and Preservation

Water Quality

Standard Values for Water Quality

Specifies standard water quality parameters and their importance for boiler longevity and warranty.

Saline Boiler Feedwater Requirements

Details the specific requirements for saline boiler feedwater quality.

Commissioning

Commissioning Sequence

Details the standard sequence of operations for boiler commissioning, including safety checks.

Safety Checks

Covers function checks for safety pressure limiters and safety valves.

Monitoring

What to Do in Event of Operating Faults

Offers guidance on immediate actions and hazard prevention during operating faults.

Repairs and Inspection

Safe Inspection of the Steam Boiler

Details safety precautions and procedures for entering and inspecting a steam boiler.

Commissioning, Inspection, Maintenance

Steps - Commissioning, Inspection and Maintenance

Provides a structured overview of commissioning, inspection, and maintenance steps with page references.

Commissioning the System

Guides through the comprehensive process of commissioning the boiler system.

Checking Water Level and System Pressure

Guides on checking the water level and system pressure during commissioning.

Checking Safety and Control Equipment

Details checks for the proper functioning of safety and control equipment.

Checking Safety Valve

Provides information on checking the safety valve.

Checking Water Quality

Guides on documenting water quality parameters like top-up volume and hardness.

Adjusting the Burner

Explains how to adjust the burner's combustion heating output and related settings.

Troubleshooting

Diagnosis

Lists common faults, their causes, and recommended measures for troubleshooting boiler issues.

Checklist

Viessmann Vitomax HS M95 Specifications

General IconGeneral