Electrical Control Function
Electrical Control System 129
1.3.3.5 High evaporator coil temp.T2 protection:
For 12K models
TEstop
T2
Resume
Off
Decrease
TEdown
TEnorm
Hold
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
For other models:T2>60, the compressor will stop and restart when T254.
1.3.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between
17~30.
In auto mode, the machine will choose cooling, heating or fan-only mode according to T (T =T1-Ts).
For 12K models:
T=T1-Ts Running mode
T1
Cooling
-1<T1
Fan-only
T-1
Heating
For other models:
T=T1-Ts Running mode
T2
Cooling
-1≤∆T<2
Fan-only
T<-1
Heating
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating and cooling, the compressor will keep stopping for 15
minutes and then choose mode according to T1-Ts.
If the setting temperature is modified, the machine will choose running function again.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vivax ACP-12CC35AECI and is the answer not in the manual?

Vivax ACP-12CC35AECI Specifications

General IconGeneral
BrandVivax
ModelACP-12CC35AECI
CategoryAir Conditioner
LanguageEnglish

Related product manuals