Page 28
5.4 Technical Data
5.4.1 B-Series Boilerhouse (BHE)
MODEL
B70HE
B90HE
B120HE
Nominal
Heat Output
kW
Btu/hr
14.7
50,000
17.6
60,000
21.0
71,650
21.0
71,560
23.5
80,000
27.1
92,380
27.1
92,380
29.0
99,050
32.7
111,600
Nominal
Heat Input
kW
Btu/hr
15.3
52,150
18.4
62,600
22.0
75,000
22.0
75,000
24.4
83,175
28.0
95,550
28.0
95,550
30.0
102,400
34.0
116,000
Burner
RDB 2.2 15-21
RDB 2.2 21-26
RDB 2.2 26-33
Head
T1SH
T2SH
T5S
Secondary Air Damper
B
N/A
N/A
Conventional
Flue Diameter
mm
in
100 or 125
4 or 5
100 or 125
4 or 5
100 or 125
4 or 5
Flue Gas Temp.
0
C
86
88
90
90
93
95
95
98
110
Smoke
Bacarach
0
0
0
Kerosene Settings
Nozzle
make
Danfoss 60°ES
Danfoss 60°ES
Danfoss 60°ES
size
0.5
0.5
0.6
0.6
0.65
0.75
0.75
0.85
0.85
Oil Pump
Pressure
bar
psi
7.0
102
9.0
130
8.0
116
8.0
116
8.0
116
7.0
102
7.0
102
8.0
116
10.0
145
Max CO
2
%
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
Approx Fuel
Flow Rate
litres/h
Gals/h
1.65
0.36
1.98
0.44
2.35
0.52
2.35
0.52
2.65
0.58
2.98
0.65
2.98
0.65
3.40
0.75
3.81
0.84
Flow Connection
1” BSP Female
1” BSP Female
1” BSP Female
Return Connection
1” BSP Female
1” BSP Female
1” BSP Female
Water
Content
litres
gals
22
4.8
22
4.8
22
4.8
Boiler Weight Dry
kg
78
78
78
Boiler Weight Wet
kg
100
100
100
SEDBUK Efficiency 2009
90.7%
90.7%
90.8%
Factory Settings
Highlighted in bold

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WarmFlow Utility Combi UC70HEE and is the answer not in the manual?

WarmFlow Utility Combi UC70HEE Specifications

General IconGeneral
BrandWarmFlow
ModelUtility Combi UC70HEE
CategoryBoiler
LanguageEnglish

Related product manuals