EasyManua.ls Logo

WarmFlow Utility Combi UC70HEE - Page 41

Default Icon
107 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 40
K-Series Kabin Pak System (KSHE)
MODEL
KS70HE
KS90HE
KS120HE
Nominal
Heat Output
kW
Btu/hr
14.7
50,000
17.6
60,000
21.0
71,650
21.0
71,560
23.5
80,000
27.1
92,380
27.1
92,380
29.0
99,050
32.7
111,600
Nominal
Heat Input
kW
Btu/hr
15.3
52,150
18.4
62,600
22.0
75,000
22.0
75,000
24.4
83,175
28.0
95,550
28.0
95,550
30.0
102,400
34.0
116,000
Burner
RDB 2.2 15-21
RDB 2.2 21-26
RDB 2.2 26-33
Head
T1SH
T2SH
T5S
Secondary Air Damper
B
N/A
N/A
Conventional
Flue Diameter
mm
in
100 or 125
4 or 5
100 or 125
4 or 5
100 or 125
4 or 5
Flue Gas Temp.
0
C
86
88
90
90
93
95
95
98
110
Smoke
Bacarach
0
0
0
Kerosene Settings
Nozzle
make
Danfoss 60°ES
Danfoss 60°ES
Danfoss 60°ES
size
0.5
0.5
0.6
0.6
0.65
0.75
0.75
0.85
0.85
Oil Pump
Pressure
bar
psi
7.0
102
9.0
130
8.0
116
8.0
116
8.0
116
7.0
102
7.0
102
8.0
116
10.0
145
Max CO
2
%
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
Approx Fuel
Flow Rate
litres/h
Gals/h
1.65
0.36
1.98
0.44
2.35
0.52
2.35
0.52
2.65
0.58
2.98
0.65
2.98
0.65
3.40
0.75
3.81
0.84
Flow Connection
22mm Copper
22mm Copper
22mm Copper
Return Connection
1” BSP Female
1” BSP Female
1” BSP Female
Water
Content
litres
gals
22
4.8
22
4.8
22
4.8
Boiler Weight Wet
kg
138
138
138
SEDBUK Efficiency 2009
90.7%
90.8%
90.7%
Factory Settings
Highlighted in bold

Table of Contents

Related product manuals