EasyManua.ls Logo

Watlow 988 series - Page 35

Watlow 988 series
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Description Read (?) and/or Write (=) Syntax Range
data.1 data.2
Modbus
Address
Ramping Controller Prompt Table
981,
982, 983, 984
Command Summary Series 981-984, Chapter 5 Data Communications with the Watlow Series 988 Family
5.7
IDSP Idle Set Point ? <sp> IDSP <cr> RL1 to RH1
308 After Power Outage = <sp> IDSP <sp> data.2 <cr>
IN1 Input 1 Type ? <sp> IN1 <cr> 1 = J t/c; 32 to 1500°F/0 to 816°C
601 = <sp> IN1 <sp> data.2 <cr> 2 = K t/c; -328 to 2500°F/-200 to 1371°C
3 = T t/c; -328 to 750°F/-200 to 399°C
4 = N t/c; 32 to 2372°F/0 to 1300°C
5 = E t/c; -328 to 1470°F/-200 to799°C
6 = C t/c (W3); 32 to 4200°F 0 to 2316°C
7 = D t/c (W5); 32 to 4200°F/0 to 2316°C
8 = Pt 2; 32 to 2543°F/0 to 1395°C
10 = R t/c; 32 to 3200°F/0 to 1760°C
11 = S t/c; 32 to 3200°F/0 to 1760°C
12 = B t/c; 1598 to 3300°F/870 to 1816°C
Caution: Writing to IN1 or IN2 resets most 14 = 1° RTD (JIS); -328 to 1166°F/-200 to 630°C, or
prompts to their default values. 14 = 1° RTD (DIN); -328 to 1472°F/-200 to 800°C
15 = 0.1° RTD; -99.9 to 999.9°F/-99.9 to 700.0°C
17 = 4-20mA; -999 to 9999 units
18 = 0-20mA; -999 to 9999 units
19 = 0-5VÎ (dc); -999 to 9999 units
20 = 1-5VÎ (dc); -999 to 9999 units
21 = 0-10VÎ (dc); -999 to 9999 units
23 = 0-50mVÎ (dc); -999 to 9999 units
24 = 0-100mVÎ (dc); -999 to 9999 units
IN2 Input 2 Type ? <sp> IN2 <cr> 26 = Slidewire off
611 = <sp> IN2 <sp> data.2 <cr> 27 = Slidewire; 100 to 1200
32 = Event input 2 off
33 = Event Input 2 on
IT1 Integral for Output 1 ? <sp> IT1 <cr> 0.00 to 99.99 minutes per repeat
501 = <sp> IT1 <sp> data.2 <cr> Default: 10.00 minutes per repeat
IT2 Integral for Output 2 ? <sp> IT2 <cr> 0.00 to 99.99 minutes per repeat
511 = <sp> IT2 <sp> data.2 <cr> Default: 10.00 minutes per repeat
ITY1 Input 1 ? <sp> ITY1 <cr> 0 = None
8 Hardware Type 1 = t/c only
4 = Input off
5 = Universal RTD
6 = Universal high gain t/c
7 = Universal low gain t/c
8 = Universal millivolts
9 = Universal process
ITY2 Input 2 ? <sp> ITY2 <cr> 0 = None
9 Hardware Type 3 = Slidewire
4 = Input off
10 = Event input
LAT2 Alarm 2 Latching ? <sp> LAT2 <cr> 0 = Latching alarms
721 = <sp> LAT2 <sp> data.2 <cr> 1 = Non-latching alarms
Default: 1
LAT3 Alarm 3 Latching ? <sp> LAT3 <cr> 0 = Latching alarms
738 = <sp> LAT3 <sp> data.2 <cr> 1 = Non-latching alarms
Default: 1
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
Table 5.7 -
IDSP to LAT3
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.

Table of Contents

Related product manuals