EasyManua.ls Logo

Watson-Marlow 520DUN - 22.3 Speed: analogue input

Watson-Marlow 520DUN
105 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Watson-Marlow 520DuN IP66/NEMA 4X User Manual 64
22.3 Speed: analogue input
It is possible to control the speed of the pump remotely by
one of these methods: a voltage analogue signal within the
range 0-10V; or a current analogue signal within the range
4-20mA; or a remote potentiometer using the 10V supply at
J7.
The analogue process signal must be applied to the i/p ter-
minal of the Analogue 1 connector (J5). Ground to the 0V
terminal of the same connector. The pump will provide an
increasing flow rate for a rising control signal (non-inverted
response) or an increasing flow rate for a falling control sig-
nal (inverted response). See 16.2 Analogue in the Setup
menu.
4-20mA circuit impedance: 250Ω.
For voltage mode, 0-10V, a stable, reliable voltage source can be used with a DC
voltmeter. Circuit impedance: 22kΩ.
Inverting the response is set up in software. Do not invert the polarity of the termi-
nals.
A remote potentiometer with a
nominal value of between 1k and
2k with a minimum of 0.25W
should be wired between the ter-
minals of the Rem-pot connector
(J7) and the i/p terminal of the
Analogue 1 connector (J5). When
using a remote potentiometer, do not apply a voltage or cur-
rent control input signal at the same time. The speed control
signal will require calibration relative to the minimum and
maximum settings of the potentiometer. This is done in soft-
ware - see 18.1 Trim in the Setup section.
When using a remote potentiometer, it is important to set the analogue input to volt-
age in the Setup menu. Otherwise the reference voltage supply from the Rem-pot
connector will be overloaded and will not provide a full 10V.

Table of Contents