pg.14
WB-OVRC-UPS-1100/1500/2000 Owner’s Manual
SPECIFICATIONS
MODEL WB-IP-UPS-1100-1 WB-IP-UPS-1500-1 WB-IP-UPS-2000-1
CAPACITY 1100VA/990W 1500VA/1350W
1900VA/1710W @120V Output
1740VA/1566W @110V Output
INPUT
Voltage 110/120V AC
Acceptable Voltage Range 81-145V AC
Frequency Range 60/50 Hz (Auto sensing)
Power Outlet NEMA 5-15 NEMA 5-20
Power Inlet IEC C14 IEC C20
Surge Protection Modes L-N, L-G, N-G
Joule Rating (minimum) 1080J
OUTPUT
Output Voltage 110/120V AC
Outlet Quantity (1) NEMA 5-15 (1) NEMA 5-15 (1) NEMA 5-20
Connections USB, RS-232 (standard DB-9)
Voltage Regulation (Batt. Mode) ± 1.5% (before battery alarm)
Frequency Range (Batt. Mode) 50 Hz or 60 Hz ± 1 Hz
Current Crest Ratio 3:1
Harmonic Distortion 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm)
Transfer Time Typical 2-6 ms, 10 ms max.
Waveform (Batt. Mode) Pure sinewave
EFFICIENCY
AC Mode 95% 96%
Buck & Boost Mode 93% 94%
Battery Mode 88% 90%
BATTERY
Type & Number 12 V/9AH x 2 12 V/9AH x 4
Terminal Type F2 F2
Typical Recharge Time 4 hours recover to 90% capacity
Charging Current (Max.) 1.5A 1.5A 1.5A
Charging Voltage 27.4V DC ± 1% 54.8 V DC ± 1%
PROTECTION
Joule Ratings Line-neutral: 158J*2; Line-ground: 264J*2; Neutral-ground: 264J*2; Total joule rating: 1372J
INDICATORS
LCD Display AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery
ALARM
Battery Mode Sounds every 10 seconds
Low Battery Sounds every 2 seconds
Overload Sounds every 1 second
Fault Continuously sounding
PHYSICAL
Dimensions (WxHxD)
437.90 mm(17.24") x 87.88 mm (3.46")
x 409.96 mm (16.14")
437.90 mm(17.24”) x 87.88 mm (3.46”) x 510.03 mm(20.08)”
Rack Mount 2 RU
ENVIRONMENT
Maximum Operating Temperature 40 °C(104 °F)
Humidity 0-90 % RH @ 0- 40 °C (Non-condensing)
Noise Level Less than 45dB
MANAGEMENT
Smart RS-232/USB Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8/10, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser