EasyManuals Logo

Watts 909 Series Basic Installation Instructions

Watts 909 Series
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
A. All needle valves must be closed on test kit.
B. Open test cock No. 4 and ush test cocks Nos. 1, 2 and 3 on reduced pressure
assembly then close test cock No. 4.
C. Attach hoses as shown. Bleed air from kit, close No. 2 shutoff.
909QT shown
No. 2 shutoff
Bleed Valve A
Bleed Valve B
High
(red)
Bypass
(yellow)
Low
(blue)
Test No. 1 - Check Valve No.2
Purpose: To test check valve No. 2 for tightness against
reverse ow.
Requirements: Valve must be tight against reverse ow under
all pressure differentials.
Step 1 Slowly open the needle valve “A” high side (red) and “C”
bypass (yellow). Keep the “B” low (blue) closed.
Step 2 Open test cock No. 4.
Step 3 Indicated pressure differential will decrease slightly. If
pressure differential continues to decrease (until the vent
opens) the No. 2 check valve is reported as “leaking”.
Test No. 2 - Shutoff Valve No. 2
Purpose: To test shutoff valve No. 2 for tightness.
Step 1 After passing Test No. 1, continue to test No. 2 by
closing test cock No. 2.
Step 2 The indicated pressure differential will decrease slightly.
If pressure differential continues to decrease
(approaching “zero”), the No. 2 shutoff valve is reported
to be “leaking”. Note: A leaking No. 2 shutoff will give a
false reading in tests No. 3 and 4.
Test No. 3 - To Test No. 1 Check Valve
Purpose: To test check valve No. 1 for tightness.
Requirements: Valve must be tight against reverse ow under
all pressure differentials.
Step 1 Close needle valve “A” high side (red) and open test
cock No. 2
Step 2 Close test cock No. 4. Disconnect bypass hose (yellow)
at test cock No. 4.
Step 3 Open needle valve “B” low (blue) and “C” bypass
(yellow), bleeding to atmosphere, then closing needle
valve “B” (blue) restores the system to a normal
static condition.
Step 4 Observe the pressure differential gauge. If there is a
decrease in the indicated value, the No. 1 check valve is
reported as “leaking”.
Test No. 4 - Pressure Differential Relief Valve
Purpose: To test operation of pressure differential
relief valve.
Requirements: The pressure differential relief valve must
operate to maintain the “zone” between the two check valves
at least 2psi less than the supply pressure.
Step 1 Close needle valve “C” bypass (yellow).
Step 2 Open needle valve “A” high side (red).
Step 3 Open needle valve “B” low (blue) very slowly until the
differential gauge needle starts to drop.
Step 4 Hold the valve at this position and observe the gauge
reading at the moment the rst discharge is noted from
the relief valve. Record this as the opening differential
pressure of the relief valve. Note: it is important that the
differential gauge needle drops slowly.
Step 5 Close test cocks Nos. 2 and 3. Remove hose from test
cocks Nos. 2 and 3.
Step 6 Use bypass hose (yellow) to relieve pressure from test
kit by opening needle valve “A”, “B” and “C” and bleed
valves “A” and “B”.
Step 7 Remove all test equipment and open No. 2 shutoff valve
of the device.
4
CAUTION: To prevent freezing, hold Test Kit vertically to drain differential gauge and hoses prior to placing in case.
For additional testing information, send for IS-TK-DP/DL, IS-TK-9A, IS-TK-99E or IS-TK-99D.
Test Procedure for Reduced Pressure Assembly

Other manuals for Watts 909 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts 909 Series and is the answer not in the manual?

Watts 909 Series Specifications

General IconGeneral
Series909
CategoryControl Unit
Body MaterialBronze
Connection TypeThreaded
Temperature Range33°F-180°F
Size Range1/2" - 2"
End ConnectionsThreaded

Related product manuals