Benchmark 750-3000 Boiler Installation & Startup Manual
SECTION 6 BOILER SEQUENCING TECHNOLOGY
OMM-0121_D GF-205 5/9/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 114 of 122
OPTION 8 - Remote Setpoint With Modbus Header Sensor And Modbus
Setpoint Drive Instructions
Step 3: Configure ALL C-More Units
On ALL Boilers:
1. Go to the Configuration menu and set the BST Menu item to Enabled.
2. Go to the Boiler Sequencing Menu and set the BST Mode item to BST Client (for now).
On MANAGER only:
3. Go to the BST Setpoint item and enter the failsafe Setpoint.
4. Go to the BST Setup Menu item and set to Enabled.
5. Go to the BST Setpoint Mode item and select Remote Setpoint.
6. Go to the BST Remote Signal and select either Network.
7. Go to the Head Temp Source item and select Network.
8. Go to the Header Temp Addr item and enter the Modbus Address (240).
9. Go to the Header Temp Point item and enter the Modbus Point (14).
When ALL C-More units have been configured:
10. Go to the Boiler Sequencing Menu of the Manager unit and set the BST Mode item to BST
MANAGER.