Benchmark 750-3000 Boiler Installation & Startup Manual
SECTION 5 – SAFETY DEVICE TESTING
OMM-0121_D GF-205 5/9/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 94 of 122
5.9 SSOV PROOF OF CLOSURE SWITCH CHECK
The SSOV, shown in Figure 5-9, contains the Proof of Closure switch. The Proof of Closure
switch circuit is checked as follows:
SSOV Proof Of Closure Switch Check Instructions
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in MANUAL mode and set the valve position between 25% and 30%.
3. Refer to Figure 5-1a through 5-1c or 5-2 (BMK3000), above, and locate the SSOV.
4. Remove the cover from the SSOV by loosening the screw shown in Figure 5-9. Lift off the
cover to access the terminal wiring connections.
5. Disconnect wire #148 from the SSOV to “open” the Proof Of Closure switch circuit.
6. The unit should fault and display SSOV SWITCH OPEN.
7. Replace wire #148 and press the CLEAR button.
8. Set the ON/OFF switch to the ON position to start the unit.
9. Remove the wire again when the unit reaches the purge cycle and PURGING is
displayed.
10. The unit should shut down and display SSOV FAULT DURING PURGE.
11. Replace the wire on the SSOV and press the CLEAR button. The unit should restart.
Figure 5-9: SSOV Actuator Cover Location
5.10 PURGE SWITCH OPEN DURING PURGE
The Purge switch (and Ignition switch) is located on the Air/Fuel Valve. To check the switch,
proceed as follows:
Purge Switch Open During Purge Check Instructions
1. Set the unit’s ON/OFF switch to the OFF position.
2. Place the unit in MANUAL mode and set the valve position between 25% and 30%.
3. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it (see
Figure 5-10a and 5-10b).
4. Remove one of the two wires (#171 or #172) from the Purge switch (Figure 5-11a and 5-
11b).
5. Initiate a unit start sequence.
SSOV
ACTUATOR
COVER
ACTUATOR
COVER
SCREW