EasyManuals Logo

Watts Benchmark Aerco OMM-0122 User Manual

Watts Benchmark Aerco OMM-0122
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
Benchmark 750-3000 Boiler Installation & Startup Manual
SECTION 2 INSTALLATION
OMM-0121_D GF-205 5/9/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 35 of 122
Outdoor Air
Air Sensor Common
Air Temp Sensor
O2 Sensor
Not Used
Spark Signal +
Spark Signal
O2 Sensor +
Not Used
+12 V Out
Analog In +
Analog In
Valve Feedback +
Valve Feedback
Shield
Shield
Analog Out +
Analog Out
RS-485 +
RS-485 Ground
RS-485 -
RS-232 - TxD
RS-232 - RxD
VFD/Blower +
VFD/Blower
Remote Intl’k OUT
Remote Intl’k IN
NOT USED
Delayed Intl’k OUT
Delayed Intl’k IN
Not Used
Fault Relay N.C.
Fault Relay COMM
Fault Relay N.O.
Aux Relay N.C.
Aux Relay COMM
Aux Relay N.O.
Not Used
NOTE:
Refer to this image for connections rather than the silkscreen labels shown on the board.
Figure 2-11: I/O Box Terminal Strips
2.11.1 Outdoor Air & Air Sensor Common
An outdoor temperature sensor (P/N 61047) is required for the INDOOR/OUTDOOR RESET
mode of operation. It can also be used with another mode if it is desired to use the outdoor
sensor enable/disable feature, which allows the boiler to be enabled or disabled based on the
outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an
enable/disable outdoor temperature, see Section 2.6: CONFIGURATION Menu, item 7, in the
Benchmark 750 3000 Operation and Maintenance Guide, OMM-0122 (GF-206).
The outdoor sensor may be wired up to 200 feet (61m) from the boiler. It is connected to the
OUTDOOR AIR and AIR SENSOR COMMON terminals of the I/O board (Figure 2-11). Wire the
sensor using a twisted shielded pair wire from 18 to 22 AWG. There is no polarity to observe
when terminating these wires. The shield is to be connected only to the terminals labeled
SHIELD in the I/O Box PCB. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an
average outside air temperature is expected. The sensor must be shielded from direct sunlight
as well as impingement by the elements. If a shield is used, it must allow for free air circulation.
Relay Contacts:
120 VAC, 30 VDC
5 Amps, Resistive
DANGER!
120 VAC USED
IN THIS BOX
DIP 1 Modbus Term
DIP 2 RS232 Enable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Benchmark Aerco OMM-0122 and is the answer not in the manual?

Watts Benchmark Aerco OMM-0122 Specifications

General IconGeneral
BrandWatts
ModelBenchmark Aerco OMM-0122
CategoryBoiler
LanguageEnglish

Related product manuals