Benchmark 750-3000 Boiler Installation & Startup Manual
SECTION 2 INSTALLATION
OMM-0121_D GF-205 5/9/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 17 of 122
2.4.2 Setting the Unit
All Benchmark Boilers must be installed on a level housekeeping pad to ensure proper
condensate drainage. The pad thickness must be:
BMK 750 1000 4 to 6 inch (10.2 to 15.2 cm)
BMK 1500 3000 4 to 8 inch (10.2 to 20.3 cm)
If anchoring the unit, refer to Figure 2-2a, 2-2b and 2-2c for anchor locations.
All holes are flush with the bottom surface of the frame.
All dimensions shown are in inches [millimeters]
Figure 2-2a: BMK 750/1000 Anchor Bolt Locations
Figure 2-2b: BMK 1500/2000 Anchor Bolt Locations