NATURAL GAS Combustion Calibration Instructions
TABLE 4-3c: NATURAL GAS Final Valve Positions: 1500DF – 2000DF
Valve % Oxygen %
TABLE 4-3d: NATURAL GAS Final Valve Positions: BMK 2500 – 3000
Nitrogen
Oxide (NO
x
)
Carbon
Monoxide (CO)
Valve % Oxygen % Valve % Oxygen %
BMK 2500
NOTE:
If NO
x
readings exceed the target values in Table 4-3a through 4-3d, increase the O
2
level
up to 1% higher than the listed calibration range shown in the table. Record the increased
O
2
value on the Combustion Calibration sheet.
31. If the oxygen level at the lowest valve position (14%, 16% or 18%)
Blower voltage is at the minimum value, you can adjust the TAC screw, which is recessed
in the top of the Air/Fuel Valve (see Figure 4-4). Rotate the screw 1/2 turn clockwise (CW)
to add fuel and reduce the O
2
to the specified level. Recalibration MUST be performed
again from 60% down to the lowest valve position after making a change to the TAC screw.
This completes the NATURAL GAS combustion calibration procedure.