Parameter Range Description
BOILER 1 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification.
BOILER 1 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification.
BOILER SERVICE HOURS AND CYCLES REPEATED FOR BOILERS 2 TO 4
BOILER 5 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification. Available when connected to a 294EXP expansion control.
BOILER 5 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler
service alert notification. Available when connected to a 294EXP expansion control.
BOILER SERVICE HOURS AND CYCLES REPEATED FOR BOILERS 6 TO 8
BOILER 9 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler
service alert notification. Available when connected to two 294EXP expansion controls.
BOILER 9 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler service
alert notification. Available when connected to two 294EXP expansion controls.
BOILER SERVICE HOURS AND CYCLES REPEATED FOR BOILERS 10 TO 12
BOILER 13 SERVICE
HOURS ALERT
1000 to 25000 hours
Default: 5000 hours
Set the number of boiler running hours above which the control triggers a boiler service
alert notification. Available when connected to three 294EXP expansion controls.
BOILER 13 SERVICE
CYCLES ALERT
1 to 25000 cycles
Default: 25000 cycles
Set the number of boiler on/off cycles above which the control triggers a boiler service
alert notification. Available when connected to three 294EXP expansion controls.
BOILER SERVICE HOURS AND CYCLES REPEATED FOR BOILERS 14 TO 16
COMMISSIONING WIZARD
STEP 1
All equipments is off.
STEP 2
Combustion air damper is open.
STEP 3
System pump is on.
STEP 4
DHW pump is on. This only applies if DHW is enabled.
THE FOLLOWING STEPS ARE REPEATED FOR EACH AVAILABLE BOILER 1 TO 16
STEP 5A
Boiler pump or valve is on.
STEP 5B
Boiler enable is on.
STEP 5C
Boiler set to Start Mod. This only applies to modulating firing rate boilers.
STEP 5D
Boiler Mod is set to 180°F. This only applies to modulating temperature target boilers.
STEP 5E
Boiler is off.