EasyManua.ls Logo

Watts Tekmar WiFi Snow Melting Control 670 - Setup - Mixing Setup Menu

Watts Tekmar WiFi Snow Melting Control 670
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27 of 48
Setup – Mixing Setup Menu
Description Range Access
MIXING TYPE
Select the mixing output type.
Floating = Floating action mixing output to operate a mixing valve.
Injection = Injection mixing output to operate a wet-rotor, impedance protected pump with a current
less than 2.4 A.
0-10 V = Analog mixing output provides a 0-10 V (dc) signal.
4-20 mA = Analog mixing output provides a 4-20 mA signal.
Conditions: Available when Application Mode is set to Mixing or Boiler+Mix.
Floating,
Injection,
0-10 V,
4-20 mA
Default = Floating
Installer
MIX MOTOR SPEED
Set the time that the mixing actuating motor requires to operate from fully closed to fully open.
Check the mixing actuator motor instruction manual for the motor speed time.
Conditions: Available when 1) Application Mode is set to Mixing or Boiler+Mix, and 2) Mixing Type
is set to Floating, 0-10 V, or 4-20 mA.
30 to 230
seconds
Default = 105
seconds
Installer
MIX MAXIMUM
Set the maximum operating temperature of the system supply water temperature.
Conditions: Available when Application Mode is set to Mixing or Boiler+Mix.
80 to 180°F, Off
(26.5 to 82.5°C)
Default = 140°F
(60.0°C)
Installer