There are two sets of wires extending out of the control panel. The black and white wires marked “L1” and “L2” should be
connected to the 120 VAC supply line. The black and white wires marked “GV1” and “GV2” are to be connected to the
gas train. The green wire exiting the gas train must be connected to the ground lug in the control panel.
For the 120 VAC wiring to the burner, use solid copper conductor wire not lighter than #14 AWG. If a fused disconnect is
used, it should be fused for a minimum of 15 amps.
For the 120 VAC wiring from the burner to the gas train, use solid copper conductor wire not lighter than #14 AWG.
CAUTION: The burner is equipped with it’s own 24 VAC transformer. Do not add any 24 VAC power consuming device in
the 24 VAC control circuit of the burner, as it could overload the transformer.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after servicing.
NOTE: If any of the original burner wiring must be replaced, it must be replaced with #18 AWG 105 degrees C wire or
equivalent. See Section 3- Operation and Troubleshooting for applicable burner wiring diagrams.