Caution: B+ interface is always positive, B- interface is always negative; GND is for the parallel battery grounding
Port.
Caution: For Pass-through connections with bus bar the max Charge/Discharge
current must be limited to 300Adc. Above 300A it is necessary to connect each module
individually to a common bus bar
Information: Connect the cables according to the installation requirements, always
paying attention to minimize the length of the cables to avoid voltage drops.
Attention: To ensure safety and stability of the cluster always connect the Battery
Modules using the feet.
ATTENTION:
After turning on the system, close the cover lid
to protect live terminals.
Information: After each important event that causes the BMS
safety intervention, the BMS logic allows 6 reconnection
attempts during the 24 hours, for a maximum of 96 hours.