WECO 5K3-XP RACK LV-EMEA
34
Version 11/11/2021
Individual Module Setting
110 Adc Peak
(Standard 50Adc)
DC Voltage (extreme)
BMS Safety Intervention Voltage Limits
Operating Efficiency (Up to)
Operating Temp (with Derating applied)
-13°F to +149°F / -25°C to +65°C
+19.4°F to +32°F / -7°C to 0°C
Charging Temp @ Max 0.25C
+32°F to +113°F / 0°C to +15°C
+59°F to +131°F / +15°C to +55°C
Discharging Temp @ Max 0.5C
+149°F to +131°F / +65°C to +55°C
Discharging Temp @ Max 1C
+131°F to +32°F / +55°C to 0°C
Discharging Temp @ Range 0.1C to 0.5C
+32°F to +19.4°F / 0°C to -7°C
Discharging Temp @ Max 0.1C
+19.4°F to -13°F / -7°C to -25°C
1% self-discharge per month @ 77°F / 25°C
10 Years – see Limited Warranty terms
See Limited Warranty and Condition Applied
SOC vs C-Rate (standard logic for domestic ESS,
the C-Rate can be customized)
Charge: 0-10% 0,1C 10-95% 1C 95-98% 0,1C 98-100% 0,05C
Discharge: 100-15% 1C 15-10% 0,1C 10-0% 0,05C