W21 Magnet Drive System
®
| 5
Quick Guide
• Auxiliary Terminal Output Capacity
Terminal Function Definition Max Output
+10V 10V auxiliary power supply output, constitutes loop with GND. 50mA
A01/A02 Analog monitor output, constitutes loop with GND.
Max output 2mA as frequency,
voltage signal,
+24V 24V auxiliary power supply output, constitutes loop with COM. 100mA
Y
Collector open circuit output; can set the
action-object by program.
DC24V/50mA
TA1/TB1/TC1
TA2/TB2/TC2
Passive connector output; can set the action-object
by program.
3A/240VAC
5A/30VDC
• Connection Function Specification of Switch Terminals
AS
VS
GND
GND
AO2AO1
X1
X2
AI
+10V
COM
TC1
PLCTA1
A+
+24V
X7/PUL
X4
X3
X5
TB2
X6
TA2
B- Y
TB1
COM
TC2
Switch Terminal Selecting Position Function Specification
S1
K1 AO1:0~20mA or 4~20mA current output
K2 AO1:0~10V voltage output
S2
K3 AI:0~20mA or 4~20mA input current
K4 AI: 0~10V input voltage
S3
K5 AO2: 0.0~50kHz (J1 on), open collector circuit output
K6 AO2:0.0~50kHz (J1 on), active source output
S4
K7 RS485: connect with 120Ω terminal resistor
K8 RS485:connect without 120Ω terminal resistor
S5
J1 AO2:0.0~50kHz frequency output
J2 AO2:0~20mA or 4~20mA current output
J3 AO2:0~10V voltage output
S6
+24V Short +24V terminal and PLC terminal
PLC PLC terminal receiving external power input
COM Short PLC terminal and COM terminal
S7
K9 Disconnect GND terminal and PE discharge loop
K10 Connect GND terminal and PE discharge loop