ECO
®
Tec series 2 gas-fired water boiler – boiler manual
Figure158 Ratingsandengineeringdata—
ECO
Tec80/110/150/199
Notes
1 As an Energy Star Partner, WM
Technologies has determined that
ECO
Tec 80, 110, 150 and 199 boilers meet
the Energy Star guidelines for energy
eciency.
NOTE: Adjusting boiler ring rate will
aect AFUE rating.
2 Based on standard test procedures
prescribed by the United States
Department of Energy. Ratings also
referred to as CSA Output.
NOTE that only DOE Heating Capacity
and AFUE are certied by AHRI. AFUE
is also know as Annual Fuel Utilization
Eciency or Seasonal Eciency.
3 Net AHRI ratings are based on net
installed radiation of sucient quantity
for the requirements of the building
and nothing need be added for normal
piping and pickup. Ratings are based on a
piping and pickup allowance of 1.15. An
additional allowance should be made for
unusual piping and pickup loads.
4
ECO Tec boilers must be direct-vented.
ECO Tec boilers require special venting,
consistent with Category IV boiler.
Use only the vent materials and methods
specied in this manual.
ECO Te c boilers may be direct exhaust
vented with Kit option.
ECO Tec vent/air pipes can be either
2" or 3". An adapter is required for 2"
venting.
All vent and air pipe elbows must be sweep
elbows, NOT short-radius elbows.
5 Ratings shown are for sea level applications
only. For altitudes from sea level to 2,000 feet
above sea level, the
ECO Tec boiler requires
no modications and automatically derates
itself by approximately 4% per 1000 feet
above sea level.
6 All of the boilers will automatically de-rate
as vent/air pipe length increases, due to the
pressure loss through the piping. For vent/air
pipe lengths less than the maximum, the derate
equals the value above (% Input derate vs. vent
length) times vent length ÷ 100, for all except
for the 199 - 2" venting. 199 -2" derate equals
13% times vent length ÷ 50.
THEOUTDOOR SENSORSUPPLIEDWITHTHEBOILERMUSTBEINSTALLEDUNLESSEXEMPTEDBELOW:
IMPORTANT
In accordance with Section303ofthe
2007EnergyAct
, this boiler is equipped
with a feature that saves energy by
reducing the boiler water temperature as
the heating load decreases. is feature
is equipped with an override which is
provided primarily to permit the use of
an external energy management system
that serves the same function.
THISOVERRIDEMUSTNOTBEUSEDUNLESSATLEASTONEOFTHE
FOLLOWINGCONDITIONSISTRUE:
• An external energy management system is installed that reduces the boiler water
temperature as the heating load decreases.
• is boiler is not used for any space heating.
• is boiler is part of a modular or multiple boiler system having a total input of 300,000
BTU/hr or greater.
• is boiler is equipped with a tankless coil (not applicable to ECO Tec).
AHRICertiedRatings
Boiler
Model
ECO Tec
CSA
Input
Heating
Capacity
Seasonal
Eciency
Net
Water
Rating
Boiler
Water
Content
Vent/
Comb.Air
Connection
Diameter
%Inputderatevsventlength
(Values shown are at MAX
vent/air pipe length —
See Note 6)
DirectVentVentingONLY
MBH
(Note 5)
MBH
(Note 2)
AFUE, %
(Note 1)
MBH
(Note 3) Gallons
Inches
(Note 4)
Natural gas Propane
2"
Vent/air
piping
3"
Vent/air
piping
2"
Vent/air
piping
3"
Vent/air
piping
80 80 74 95.0 64 2.2 3" PVC/PP/SS 5 % –– 5 % ––
110 110 100 95.0 87 2.2 3" PVC/PP/SS 10 % 5 % 10 % 5 %
150 150 139 95.0 121 3.1 3" PVC/PP/SS 13 % 5 % 13 % 5 %
199 199 184 95.0 160 3.8 3" PVC/PP/SS 13 % 5 % 13 % 5 %