41
6618-2202
Configure the TD-36 485
Configure the IDW-90
Testing by simulating the event
Activate events – The sending modem
To make switch setting active the power must be cycled OFF -> ON.
AT&F Set the unit to factory default
AT&W Store default settings
AT*WIOP=10,50,2,3,0  Set I/O params  
Min pulse time = 100 ms (10)  
Pulse repetition = 500 ms (150) 
Trig type = Pulsed trigged (2)  
Pulse trig type = POS, pos edge (3)  
Output type  = No output (0)
AT*WIOL=1,2,5,0,0,070428000,  
Temp. high server room, 
+4670500899,1
Define SMS message on entry 1 
 Entry = 1 (1)  
Service = SMS (2)  
Retry = NEXT_ALLWAYS (5)  
Timeout = 0  
Priority = 0 Data 1 = SMS receiver number (070428000)  
Data 2 = SMS text (Temp. high server room)  
Data 3 = Service center Adress (+4670500899)  
Data 4 = SMS protocol UDP (1)
AT*WIOL=2,7,2,60,0,+4616480250  Define Transparent I/O on entry 2 
Entry = 2 (2)  
Service = TRANS (7)  
Retry = RETRY_3 (2)  
Timeout = 600s (60)  
Priority = 0  
Data 1 = Phone number of the remote IDW-90 
(+4616480250)
S3:1,3,4 OFF S3:2 ON V.110 configured for GSM
I/O input pulsed  with one puls SMS message transferred  
and transparent I/O established
AT*WIOT=1 Force sending of SMS-message at entry 1
AT*WIOT=2 Force the transparent I/O connection to be established