COMFORT-SET
®
90 SERIES
MULTI-STAGE/HEAT PUMP INSTALLATION/CONFIGURATION
This White-Rodgers Automatic Setback
Digital Thermostat uses microcomputer
technology to provide precise time and
temperature control. This thermostat offers
1F93-380: 7 Day programming; commer-
cial applications
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all
terminals combined)
INSTALLATION
WHITE-RODGERS
Part No. 37-6066B
Replaces 37-6066A
0120
DESCRIPTION
SPECIFICATIONS
the flexibility to design heating and cooling
programs that fit building needs. This
thermostat is adaptable to most 24 volt
Standard Systems:
Multi-stage gas, oil, electric.
Single-stage or two-stage compressor
heat pump.
THERMAL DATA
Setpoint Temperature Range:
45° to 99°F (7° to 37°C)
Operating Ambient Temperature:
32° to 110°F (0° to 43°C)
Operating Humidity Range:
90% non-condensing max.
Shipping Temperature Range:
-4° to 149°F (-20° to 65°C)
PRECAUTIONS
Do not short out terminals on gas valve
or primary control to test. Short or
incorrect wiring will damage thermostat
and could cause personal injury and/or
property damage.
Do not use on circuits exceeding
specified voltage. Higher voltage will
damage thermostat and could cause
shock or fire hazard.
Thermostat installation and all compo-
nents of the system shall conform to
Class II circuits per the NEC code.
To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is
complete.
Read all instructions thoroughly before
beginning installation.
CAUTION
!
WARNING
!
This thermostat is intended for use with a
low voltage system. Do not use on a line
voltage system.
Do not exceed ratings shown in the Specifi-
cations section, above. If in doubt about the
electrical ratings of your heating/cooling
system, have it inspected by a qualified
heating and air conditioning contractor or
licensed electrician.
All wiring must conform to local and
national electrical codes and ordinances.
This control is a precision instrument, and
should be handled carefully. Rough handling
or distorting components could cause the
control to malfunction.
NOTE
commercial forced air multi-stage or heat
pump systems with electric or fossil fuel
auxiliary.

Other manuals for White Rodgers 90 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the White Rodgers 90 SERIES and is the answer not in the manual?

White Rodgers 90 SERIES Specifications

General IconGeneral
Model90 Series
DisplayDigital
ProgrammableNo
CompatibilitySingle Stage Heating and Cooling Systems
Voltage24 VAC
TypeNon-Programmable
Stages1 Heat/1 Cool
Accuracy±1°F