WIKA operating instructions models DIH50, DIH52
EN
14008548.05 12/2016 EN/DE
8.1 Main menu “Measurement”
Function Factory setting
Unit
Setting the unit of the measuring range of the connected transmitter
Setting range:
mA → Ω → bar → mbar → psi → hPa → kPa → mmH2O → mH2O → inHg → °C →
°F → K → % → USER → V
mA
Measuring range start
Setting of the start value of the measuring range of the connected transmitter
(e.g. -30 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
4,000
Measuring range end
Setting the end value of the measuring range of the connected transmitter (e.g.
120 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
20,000
Measuring range format
Setting the decimal point for the measuring range of the connected transmitter.
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
0.000
Span (only DIH52)
The current measured value is applied as max. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Zero point (only DIH52)
The current measured value is applied as min. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Damping (only DIH52)
Input damping for damping the measured value.
Setting range: 0.0 … 999
0.0
Adress (only DIH52)
Setting the HART
®
address of the assigned transmitter in the multidrop mode;
for the standard current loop mode, this address must always be set to 0.
Setting range: 0 ... 15
0
8. Menu guidance