26
WIKA operating instructions models DIH50, DIH52
EN
14008548.05 12/2016 EN/DE
11. Faults
11. Faults
Fault-tree
l = 0 mA
Current loop disconnected
Voltage supply connected incorrectly
(wrong polarity)
Transmitter not connected
l > 20 mA
l < 4 mA
4 mA < l < 20 mA
but wrong values
Process temperature out of range
Sensor connected incorrectly
Sensor break or short circuit
Wrong transmitter configuration
Error messages
HART
®
communications errors are reported with the numerical codes 1 - 9. An error
message occurs when a transaction is not successful, despite being retried several times.
An error message is only displayed when an error occurs as a consequence of a command
sent from the display, i.e. only when an operation by the user leads to the error. Errors in the
communication between the control system and sensor are detected but not displayed.
The measuring value line shows “ERROR”, the status line shows “HART
®
n” whereby “n”
represents the numeric error code. The error message remains displayed until the next key
actuation takes place.
The following table shows the error codes and information regarding the failure cause and
elimination.
Error code Description Causes
1 Transmitter does not respond
2 Communication error
Parity, check sum, package length incorrect
upon receiving
Transmitter signals receive error
3 Command not implemented Command not supported by the transmitter
4 Range error
The value is outside the range supported by
the sensor
The desired unit of measure is not supported
5 Unspecified error of the
transmitter
The sensor signals an error in the status byte that
is not broken down