EasyManua.ls Logo

WIKA DIH50 - Specific Safe Use Conditions; Intrinsically Safe Circuit Parameters

WIKA DIH50
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
WIKA operating instructions models DIH50, DIH52
EN
14008548.05 12/2016 EN/DE
9.2 Specific conditions for safe use, models DIH5x-I
Installation in areas requiring EPL Ga or EPL Gb equipment
Electronic assemblies of field indicator models DIH5x-I shall be mounted inside a case
suitable for installation in EPL Ga or Gb area respectively, wherein electrostatic charge
effects are excluded. The case shall provide, as a minimum, a degree of protection of
IP20 according to IEC 60529.
Wiring inside this case shall satisfy the conditions of clause 6.3.12 and clause 7.6.e of
IEC 60079-11:2011.
Terminals or connectors for the intrinsically safe circuits shall be arranged in line with
clause 6.2.1 or 6.2.2 of IEC 60079-11:2011, respectively.
Installation in areas requiring EPL Da or EPL Db equipment
Electronic assemblies of field indicator models DIH5x-I shall be mounted inside a case
suitable for installation in EPL Da or Db area respectively, wherein electrostatic charge
effects are excluded. The case shall provide, as a minimum, a degree of protection of
IP5x (group IIIB application) or IP6x (group IIIC application) according to IEC 60529.
Wiring inside this case shall satisfy the conditions of clause 6.3.12 and clause 7.6.e of
IEC 60079-11:2011.
Terminals or connectors for the intrinsically safe circuits shall be arranged in line with
clause 6.2.1 or 6.2.2 of IEC 60079-11:2011, respectively.
9.3 Intrinsically safe supply and signal circuit, models DIHxx-B, DIHxx-NT
(4 ... 20 mA loop; terminal ⊕ and ⊖)
Parameters Models DIH5x-B, DIH5x-I
Voltage U
i
/ U
0
29 V
Strenght of current I
i
/ I
0
100 mA
Power P
i
680 mW
Effective internal capacitance C
i
13.2 nF
Effective internal inductance L
i
1.2 μH
9. Information on mounting and operation in hazardous areas