EasyManua.ls Logo

WIKA IS-3 - Adjusting the Zero Point; Adjusting the Span

WIKA IS-3
104 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45WIKA operating instructions pressure transmitter, model IS-3
MM/YYYY country code based on 14095850.02 12/2014 EN/CN
EN
A
Clamping nut Screw
7.2 Adjustingthezeropoint(gureB)
1. Connect the instrument connector (3) to the power supply and a display unit (e.g. ammeter, voltmeter) according to
the connection diagram.
2. Go to the start of the measuring range.
3.
Using potentiometer “Z”, adjust the minimum output signal (e.g. 4 mA)
7.3 Adjustingthespan(gureB)
1. Connect the instrument connector (3) to the power supply and a display unit (e.g. ammeter, voltmeter) according to
the connection diagram.
2. Go to the end of the measuring range.
3.
Using potentiometer “S”, adjust the maximum output signal (e.g. 20 mA)
4. Check the zero point and if there is any deviation, re-adjust it.
5. Repeat the procedure until the zero point and the span are set correctly.
Field case
7. Adjusting the zero point and span

Related product manuals