12 WIKA operating instructions pressure transmitter, model S-11
GB
14043046.01 06/2012 GB/D/F/E
Adjustability of zero point and span
1)
Adjustment is made using potentiometers inside the instrument.
Zero point ± 5 %
Span ± 5 %
1) Adjustment not possible for cable outlet with ingress protection IP 68
3.5 Operating conditions
Ingress protection (per IEC 60529)
The ingress protection depends on the type of electrical connection.
Electrical connection Ingress protection
Angular connector DIN 175301-803 A IP 65
Circular connector M12 x 1 (4-pin) IP 67
Cable outlet
Standard IP 67
Option IP 68
1)
1) Adjustability of zero point and span not possible
The stated ingress protection only applies when plugged in using mating connectors that have the
appropriate ingress protection.
Vibration resistance
Process connections without cooling element
20 g (IEC 60068-2-6, under resonance)
Process connections with cooling element
10 g (IEC 60068-2-6, under resonance)
3. Specications