28 WILO SE 11/2012
To ensure drip protection and strain relief at the PG screwed
connection, a connection cable with an adequate outer diame-
ter is necessary (e.g. H05W-F3G1.5 or AVMH-3x1.5).
When pumps are used in systems with water temperatures
above 90°C, a suitably heat-resistant connection cable must be
installed.
The connection cable is to be installed in such a way that it can
under no circumstances come into contact with the piping and/
or the pump and motor housing.
Make the mains connection according to Fig. 6.
The connection cable can be taken through the cable feed-in right
or left. Exchange dummy plugs and cable feed-in as necessary.
When the terminal box is positioned laterally, always arrange the
cable feed-in from below (Fig. 5).
CAUTION! Risk of short circuit!
Once electrical connection is complete and in order to pro-
tect the terminal box from moisture, the terminal box cover
must be sealed according to regulations.
Earth the pump/system according to regulations.
8Commissioning
WARNING! Risk of injury and damage to property!
Incorrect commissioning can lead to injuries to persons and
damage to property.
Commissioning by qualified personnel only!
Depending on the operating status of the pump or system
(fluid temperature), the entire pump can become very hot.
Touching the pump can cause burns!