7 Installation and electrical connection
DANGER! Risk of fatal injury!
Improper installation and electrical connection can result in fatal injury.
Danger from electrical current must be eliminated.
Installation and electrical connection may only be carried out by qualified
personnel and in accordance with the applicable regulations.
Accident prevention regulations must be observed!
Comply with the regulations of the local energy supply company!
Pumps with pre-assembled cable:
Never pull on the pump cable
Do not kink the cable.
Do not place any objects on the cable
7.1 Installation
WARNING! Danger of bodily injury!
Incorrect installation can result in injuries.
There is a crushing hazard
There is a risk of injury due to sharp edges/burrs. Wear appropriate protec-
tive clothing (e.g. safety gloves)!
There is a risk of injury hazard due to the pump/motor falling. Use suitable
lifting gear to secure the pump/motor against falling.
CAUTION! Risk of damage to property!
Incorrect installation can result in damage to property.
Only have installation work performed by qualified personnel.
Observe national and regional regulations.
When the pump needs to be transported, it may be carried only by the motor/
pump housing. Not by the module/terminal box!
Installation within a building:
Install the pump in a dry, well-ventilated room. Ambient temperatures below
-20 °C are not permitted.
Installation outside a building (outdoor installation):
Install the pump in a sump (e.g. light sump, ring sump) with cover or in a cup-
board/housing as weather protection. Ambient temperatures below -20 °C
are not permitted.
Avoid exposure of the pump to direct sunlight.
The pump requires protection so that the condensate drain grooves are not
contaminated. (fig. 6).
Protect the pump against rain. Dripping water from above is permitted pro-
vided that the electrical connection has been established in accordance with
the installation and operating instructions and properly sealed.