Installation and operating instructions Wilo-TOP-S/-SD/-RL/-I 37
English
The setting of any thermal tripping that is fitted must correspond to the maxi-
mum current (see rating plate) of the speed stage at which the pump is being
operated.
Motor protection tripping devices
If Wilo tripping units SK 602 (N)/ SK 622 (N) are present in existing systems,
pumps with full motor protection (WSK) can be connected to them. Perform the
mains connection and also the tripping unit connection (refer to the rating plate
data) in accordance with the circuit diagram fig. 7a:
1~230 V: 320 W P
1
max 400 W, with thermal winding contact
Pump with terminal
box type
Tripping SSM Fault
acknowledgement
TOP-S
TOP-SD
TOP-RL
TOP-I
1~230 V
1
(P
1
max 265 W)
Internal switching off
of motor voltage
-
Automatically, after the
motor has cooled down
2
(P
1
max 265 W)
Internal switching off
of motor voltage
-
Automatically, after the
motor has cooled down
3
(320 W P
1
max
400 W)
Thermal winding con-
tact and external trip-
ping unit (SK602 (N)/
SK622 (N) or other
switch gear/control
device)
-
Manually at the tripping
unit, after the motor on
the SK602/SK622 has
cooled down
on the SK602N/SK622N:
automatically
4
(320 W P
1
max
400 W)
Thermal winding con-
tact and external trip-
ping unit (SK602 (N)/
SK622 (N) or other
switchgear/control
device)
-
Manually at the tripping
unit, after the motor on
the SK602/SK622 has
cooled down
on the SK602N/SK622N:
automatically
5
(650 W P
1
max
960 W)
All-pole deactivation
by the integral trip
electronics
Tripping the SSM is
performed in paral-
lel with deactiva-
tion of the integral
trip electronics
Manually at the pump,
after the motor has
cooled down
Pump with terminal
box type
Tripping SSM Fault
acknowledgement
TOP-S
TOP-SD
TOP-I
3~400 V
6
(P
1
max 270 W)
Internal switching off
of a motor phase
-
Switch off mains
voltage
Allow motor to cool
down
Switch on mains volt-
age
7
(305 W P
1
max
3125 W)
All-pole deactivation
by the integral trip
electronics
Tripping the SSM is
performed in paral-
lel with deactiva-
tion of the integral
trip electronics
Manually at the pump,
after the motor has
cooled down