Ölpumpe COB-20/29/40 - Einstellung Pumpendruck
Oil pump COB-20/29/40 - Setting pump pressure
Werkseinstellung Pumpendruck COB-20/29 /
factory setting pump pressure COB-20/29
ST 1 (Stufe 1/Stage 1) = 8,5 ± 1,0 bar
ST 2 (Stufe 2/Stage 2) = 16,8 ± 2,5 bar
Einstellung Pumpendruck COB-40 /
Setting pump pressure COB-40
COB-40 COB-29 COB-20 COB-15
ST1
ST2
ST1
ST2
SW 8
1½ x
½ x
SW 8
¼ x
¼ x
Pumpendruck /
Pump pressure
ST1
ST2
11,0 ± 1,0 bar
23,5 ± 2,5 bar
9,8 ± 1,0 bar
18,0 ± 2,5 bar
8,5 ± 1,0 bar
16,8 ± 2,5 bar
Kurzbedienungsanleitung -
Short operating instructions

Other manuals for Wolf COB-40

Questions and Answers

  • R
    ricardo40Aug 20, 2025
    How to fix HLSC excess temp on Wolf COB-40?
    • R
      Robert StantonAug 20, 2025
      If the Wolf Boiler's flow temperature exceeds 110 °C, it triggers the HLSC excess temperature error. To resolve this, you should test the heating circuit pump, vent the system, press the reset button, and clean the heat exchanger.
  • K
    karensmithAug 22, 2025
    What to do if Wolf COB-40 shows flue gas sensor, excess temperature?
    • M
      Mark CrosbyAug 22, 2025
      If the flue gas temperature on your Wolf Boiler has exceeded 120 °C, triggering the flue gas sensor, excess temperature error, you should clean the heat exchanger. Also, verify that all displacement devices are installed, check the flow through the boiler, ensure the flow and return are properly connected, and then press the reset button.
  • G
    gregoryoconnellAug 25, 2025
    What to do if Wolf COB-40 displays temperature limiter - excess temperature?
    • T
      Tommy Mills DDSAug 25, 2025
      If the flow in your Wolf Boiler exceeds the temperature limiter's limit of 100 °C, triggering the temperature limiter excess temperature error, you should vent the system and check the heating circuit pump.
  • I
    Isaiah LawsonAug 26, 2025
    Why Wolf Boiler has none flame established?
    • D
      Dawn WalkerAug 26, 2025
      If your Wolf Boiler fails to establish a flame, it could be due to several reasons: a contaminated inspection window for the flame monitor/mixer head, a faulty flame monitor, air in the oil line, excessive negative or overpressure at the oil pump, or a contaminated boiler. Suggested solutions include: checking the oil line and fuel level, inspecting the ignition electrode and transformer, pressing reset, cleaning the inspection window, checking the flame monitor and lead, ensuring proper condensate drainage, or arranging for professional service.
  • J
    Jerry FaulknerAug 28, 2025
    What to do if Wolf Boiler has flame failure during operation?
    • N
      Nancy CookAug 28, 2025
      If the Wolf Boiler experiences flame failure during operation, it may be due to excessive negative pressure on the oil pump, flue gas return in the supply air, or a contaminated boiler. To address this, check CO values, inspect the flame monitor and lead, press reset, check the fuel system for leaks, or seek professional service.
  • C
    Christopher LynchAug 30, 2025
    How to fix flue gas/supply air damper that does not respond on Wolf COB-40 Boiler?
    • J
      jperezAug 30, 2025
      If the Wolf Boiler's flue gas/ventilation air damper contact (E1) fails to close or open when there is a demand, you should check the flue gas/ventilation air damper and its wiring.
  • J
    Joseph HamiltonSep 1, 2025
    Why Wolf Boiler has insufficient heating system heating, frequent cycling?
    • A
      Amanda CisnerosSep 1, 2025
      If your Wolf Boiler is not sufficiently heating the system and is cycling frequently, it could be due to air in the heating or cylinder system. You should vent the radiators, cylinder primary circuit, heating circuit pumps, and the boiler itself.
  • R
    Raymond LopezSep 3, 2025
    How to fix faulty boiler sensor on Wolf Boiler?
    • M
      Martha HaynesSep 3, 2025
      If the Wolf Boiler shows a faulty boiler sensor, it indicates a problem with the sensor or its lead. Check the sensor and lead to resolve this issue.
  • S
    Shannon LinSep 5, 2025
    How to fix faulty cylinder sensor SF on Wolf Boiler?
    • H
      Holly AdamsSep 5, 2025
      If the Wolf Boiler displays a faulty cylinder sensor SF, it indicates an issue with the sensor or its lead. Check the sensor and lead to resolve the problem.
  • T
    Teresa JonesSep 6, 2025
    How to fix outside temperature sensor faulty on Wolf COB-40 Boiler?
    • M
      Miguel RaySep 7, 2025
      If the Wolf Boiler indicates a faulty outside temperature sensor, it means there is an issue with the sensor or its lead. Check the sensor and lead.

Summary

Oil Pump COB-20;29;40 Setting Pump Pressure

Factory Setting Pump Pressure COB-20;29

Defines factory set pressure for stages 1 and 2 for COB-20/29 pumps.

Setting Pump Pressure COB-40

Details pressure adjustment for COB-40 pumps, showing ST1 and ST2 settings.

Oil Pump COB-2-20;29;40 Setting Pump Pressure

Factory Setting Pump Pressure COB-2-20

Specifies factory set pressure for stages 1 and 2 for COB-2-20 pumps.

Setting Pump Pressure COB-2-29;40

Outlines pressure adjustment for COB-2-29/40 pumps, detailing ST1 and ST2 settings.

Wolf COB-40 Specifications

General IconGeneral
TypeCondensing Boiler
Standard Efficiency98%
Heating Capacity40 kW
Operating Pressure3 bar
Efficiency98%
Fuel TypeNatural Gas

Related product manuals