Ölpumpe COB-20/29/40 - Einstellung Pumpendruck
Oil pump COB-20/29/40 - Setting pump pressure
Werkseinstellung Pumpendruck COB-20/29 /
factory setting pump pressure COB-20/29
ST 1 (Stufe 1/Stage 1) = 8,5 ± 1,0 bar
ST 2 (Stufe 2/Stage 2) = 16,8 ± 2,5 bar
Einstellung Pumpendruck COB-40 /
Setting pump pressure COB-40
COB-40 COB-29 COB-20 COB-15
ST1
ST2
ST1
ST2
SW 8
1½ x
½ x
SW 8
¼ x
¼ x
Pumpendruck /
Pump pressure
ST1
ST2
11,0 ± 1,0 bar
23,5 ± 2,5 bar
9,8 ± 1,0 bar
18,0 ± 2,5 bar
8,5 ± 1,0 bar
16,8 ± 2,5 bar
Kurzbedienungsanleitung -
Short operating instructions

Other manuals for Wolf COB-40

Questions and Answers

  • D
    Dr. Mikayla HowardSep 9, 2025
    How to fix faulty stratification sensor on Wolf Boiler?
    • D
      Dana EvansSep 9, 2025
      If the Wolf Boiler displays a faulty stratification sensor, it indicates a problem with the stratification cylinder sensor or its lead. Check the sensor and lead to resolve this.
  • D
    David McdanielSep 12, 2025
    How to fix header sensor fault on Wolf COB-40?
    • X
      Xavier WilliamsSep 12, 2025
      If the Wolf Boiler indicates a faulty header sensor, there is likely an issue with the sensor or its lead. Check the sensor and lead to troubleshoot.
  • M
    mary76Sep 13, 2025
    Why Wolf COB-40 has insufficient water pressure?
    • D
      Donald WilsonSep 13, 2025
      If the Wolf Boiler displays insufficient water pressure, it's because the pressure switch isn't activating due to low water pressure (below 0.8 bar). Ensure the system pressure is above 1.5 bar, inspect the water pressure switch and its lead, and then press the reset button.
  • E
    Eric HallSep 15, 2025
    What to do if Wolf COB-40 condensate pump not pumping?
    • K
      kadamsSep 15, 2025
      If the condensate pump in your Wolf Boiler is not pumping, it could be due to a defective pump, a blocked drain line, or a missing power supply. Check the pump itself, inspect the drain line for blockages, and verify the mains plug and fuse.
  • Y
    Yvette RyanSep 17, 2025
    Why Wolf COB-40 Boiler has max cylinder heating time exceeded?
    • A
      Ashley FosterSep 17, 2025
      If the Wolf Boiler exceeds the maximum cylinder heating time, it means the set cylinder temperature hasn't been reached with sufficient flow. Try venting the cylinder, increasing the cylinder heating time (HG20), and checking the cylinder sensor installation.

Summary

Oil Pump COB-20;29;40 Setting Pump Pressure

Factory Setting Pump Pressure COB-20;29

Defines factory set pressure for stages 1 and 2 for COB-20/29 pumps.

Setting Pump Pressure COB-40

Details pressure adjustment for COB-40 pumps, showing ST1 and ST2 settings.

Oil Pump COB-2-20;29;40 Setting Pump Pressure

Factory Setting Pump Pressure COB-2-20

Specifies factory set pressure for stages 1 and 2 for COB-2-20 pumps.

Setting Pump Pressure COB-2-29;40

Outlines pressure adjustment for COB-2-29/40 pumps, detailing ST1 and ST2 settings.

Wolf COB-40 Specifications

General IconGeneral
TypeCondensing Boiler
Standard Efficiency98%
Heating Capacity40 kW
Operating Pressure3 bar
Efficiency98%
Fuel TypeNatural Gas