Contractor level parameters
Each time the burner is shut down in heating mode, it will be
blockedforthedurationoftheburnercycleblock.
TheburnercycleblockisresetbyswitchingtheON/OFFswitch
OFFandONorbybrieypressingtheresetbutton.
Individual setting: ______
Burner cycle block
Parameter HG09
HG09
4
Factorysetting:4min
Settingrange:1to30min
Thisfunctionlimitstheboilerwatertemperatureupwardsinheating
mode,andtheburnershutsdown.Thisparameterhasnofunction
duringcylinderheating,andtheboilerwatertemperaturemayalso
behigherduringthistime."Re-heatingeffects"canresultinthe
temperaturebeingexceededalittle.
Individual setting: ______
Maximum limit
Boiler circuit TV-max.
Parameter HG08
HG08
75
Factorysetting:75°C
Settingrange:30to90°C
Subjecttotherebeingnoheatdemandfromtheheatingcircuits,
theboilercircuitpumpwillrun-oninaccordancewiththesettime,
topreventaboilersafetyshutdownathightemperatures.
Individual setting: ______
Run-on time
Boiler circuit pump
Parameter HG07
HG07
3
Factorysetting:3min
Settingrange:0to30min
Programmable input E1
Parameter HG13
HG13
1
Factorysetting:1
Settingrange:1to11
ThefunctionsofinputE1canonlybescannedandadjustedwith
WolfcontrolaccessorieswitheBUScapability.
ThefollowingfunctionscanbeallocatedtoinputE1:
No. Explanation
1 Roomthermostat
WithopeninputE1,heatingoperationwillbeblocked
(summermode),independentofanydigitalWolf
controlaccessories.
Exception:Remotecontrolledheatingcircuits