Contractor level parameters
No. Explanation
2 Maximumthermostat
Toenabletheburner,inputE1mustbeclosed.The
burnerwillremainblockedforaslongasthecontactis
open,eveninemissionstestmode,cascademodeand
forDHWandcentralheatingfrostprotectionmode.
3 N/A
4 N/A
5 Fluegasdamper/ventilationairdamper
Functionmonitoringoftheuegasdamper/
ventilationairdamperwithoatingcontact.Closed
contactConditionforburnerenableincentral
heating,DHW,cascadeandemissionstestmode.
Important: A1 (HG 14 = 7) must be programmed for
ue gas damper / ventilation air damper
function.
6 DHWcirculationpushbutton(onsite)
Afteractivatingthisbutton,theDHWcirculationpump
isoperatedfor5minutes,independentof
thetimeprogramorthepositionoftheprogram
selector(BM).
Important: In any case, output A1 must be
programmed to setting 13.